| Plan Review Notes For Permit 02121233 |
| Permit Number |
02121233 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-01-06 00:00:00 | *********** UNSAT ************** | | | | | | 1)NOTE: PLEASE SEE FIRE REVIEW COMMENTS | | | FOR EM/EXT LTS. PLEASE ALSO SHOW PER | | | 700-12E FOR CIRCUITING. | | | | | | 2)NOTE: PLEASE NOTE CIRCUIT FOR SIGN | | | SHOWN AS STEAM TABLE ON PANEL "B". | | | | | | 3)NOTE: PLEASE PROVIDE AIC RATING FOR | | | NEW DISC`S SHOWN ON RISER DIAGRAM. | | | 110-9/215-5 | | | | | | 4)NOTE: PLEASE CLARIFY EQUIPMENT GROUND- | | | ING METHOD BETWEEN MAIN DISC`S AND PANEL | | | -S. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|