Plan Review Notes
Plan Review Notes For Permit 02121190
Permit Number 02121190
Review Stop E
Sequence Number 1
Notes
Date Text
2003-01-13 00:00:00********* NOTES REDLINED ********
  
 PLEASE SEE ITEMS REDLINED ON PLANS AND
 REVISE BEFORE ROUGH.
  
 MISSING RECEPT KITCHEN COUNTERSPACE,
 210-52C-1
 GFI PROTECTION FOR ISLAND RECEPT.210-8-
 A-6.
 MISSING RECEPT FOR A/C EQUIPMENT 210-63
  
 PLEASE SUBMIT THE ABOVE ALONG WITH ANY
 OPTS THAT HAVE CHANGED BEFORE ROUGH.
 IF THERE ARE ANY QUESTIONS,PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372