| Plan Review Notes For Permit 02121190 |
| Permit Number |
02121190 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-01-13 00:00:00 | ********* NOTES REDLINED ******** | | | | | | PLEASE SEE ITEMS REDLINED ON PLANS AND | | | REVISE BEFORE ROUGH. | | | | | | MISSING RECEPT KITCHEN COUNTERSPACE, | | | 210-52C-1 | | | GFI PROTECTION FOR ISLAND RECEPT.210-8- | | | A-6. | | | MISSING RECEPT FOR A/C EQUIPMENT 210-63 | | | | | | PLEASE SUBMIT THE ABOVE ALONG WITH ANY | | | OPTS THAT HAVE CHANGED BEFORE ROUGH. | | | IF THERE ARE ANY QUESTIONS,PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|