| Plan Review Notes For Permit 02121047 |
| Permit Number |
02121047 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-12-27 00:00:00 | ************* UNSAT *************** | | | | | | 1)NOTE: PLEASE NOTE, DUE TO PANEL BEING | | | LOCATED IN SPACE NEXTDOOR. PLEASE | | | PROVIDE ACCESS TO ELECTRICAL ROOM FROM | | | ONE SPACE TO ANOTHER. PLEASE NOTE, EVEN | | | IF SAME TENANT USES BOTH SPACES, THAT | | | MAY CHANGE OR TENANT MAY MOVE OUT. ONE | | | TENANT MUST HAVE ACCESS TO THEIR BRKRS | | | FOR TURNING ON OR OFF POWER. IF ONE | | | TENANT IS AWAY, THE OTHER MAY BE "LOCKED | | | OUT". PLEASE ALSO SEE FIRE COMMENTS FOR | | | ANY CONDITIONS THEY MAY HAVE WITH DOOR | | | ACCESS/ AND/OR EXITING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|