Plan Review Notes
Plan Review Notes For Permit 02121033
Permit Number 02121033
Review Stop B
Sequence Number 1
Notes
Date Text
2002-12-24 00:00:00BUILDING DENIED
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE PLANS AND DOCUMENTS SUBMITTED DO
 NOT MEET THE REQUIREMENTS OF THE
 CONSTRUCTION BOARD OF ADJUSTMENTS AND
 APPEALS, WHICH REQUIRE THE EXISTING
 STRUCTURE TO MEET OR BE BROUGHT UP TO
 THE CURRENT CODE. THE CURRENT CODE IS
 THE 2001 FLORIDA BUILDING CODE.
  
 3)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 4)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR EXTERIOR DOORS.
  
 5)PROVIDE (2) PRODUCT APPROVALS, KEY
 PLANS AND INSTALLATION SCHEDULES
 INDICATING THE SPECIFIC TYPES OF ANCHORS
 TO BE USED FOR STORM PANELS.FBC 1606.1.4
 AND CITY AMENDMENTS 104.2.1.2
  
 6) SPECIFY THAT ADEQUATE SUBSTRATE IS TO
 BE PROVIDED FOR THE ATTACHMENT OF THE
 STORM PANELS.
  
 7) PROVIDE ENERGY CALCULATIONS REQUIRED
 BY FBC CHAPTER 13.
  
 8) PROVIDE SECTIONS OF EXTERIOR AND
 INTERIOR BEARING WALLS. CITY AMENDMENTS
 104.2.1.2
  
 9) INDICATE THE LOCATION OF ALL INTERIOR
 BEARING WALLS ON THE PLANS. CITY
 AMENDMENTS 104.2.1.2
  
 10) PROVIDE A ROOF FRAMING PLAN. CITY
 AMEND.104.2.1.2
  
 11) INDICATE THE MEAN ROOF HEIGHT, THE
 ROOF PITCH OF THE FLAT AND SLOPED ROOFS
 AS INDICATED ON THE ENGINEER'S DRAWINGS
 THAT WERE SUBMITTED. CITY AMENDMENTS
 104.2.1.2
  
 12) SPECIFY THE ROOF AND WALL SHEATHING
 MATERIAL AND FASTENING REQUIREMENTS AND
 INDICATE COMPLIANCE WITH DIAPHRAGM AND
 SHEAR WALL REQUIREMENTS. FBC 2310 AND
 CITY AMENDMENTS TABLE 2306.1
  
 13) INDICATE THE NEGATIVE AND POSITIVE
 WINDLOAD PRESSURES AT ALL EXTERIOR
 WINDOW AND DOOR OPENINGS. FBC CHAPTER 16
  
 14) SPECIFY THE GROUND CLEARANCE TO WOOD
 SHEATHING AND FRAMING. FBC 2304
  
 15) SPECIFY CRAWL SPACE VENTILATION PER
 FBC 1804.6.3.1 AND ACCESS (IF USABLE
 CRAWL SPACE) PER 1804.6.3.2.
  
 16) SPECIFY ATTIC ACCESS PER FBC 2309.6.
  
 17) PROVIDE CALCULATIONS FOR REQUIRED
 NET FREE VENTILATING AREA AS REQUIRED BY
 FBC 2309.7.
  
 18) INDICATE THE LOCATION OF THE WATER
 HEATER AND SPECIFY IF GAS OR ELECTRIC.
 FBC 2901 AND FPC 502.4.
  
 19) PROVIDE BUCK DETAILS FOR WINDOWS AND
 DOORS. FBC 1707.4
  
 20) THE BATHROOM MUST HAVE A DOOR THAT
 PROVIDES A 29 INCH CLEAR OPENING. FBC
 CHAPTER 11
  
 21) SPECIFY EGRESS WINDOWS IN ALL ROOMS
 USED FOR SLEEPING PER FBC 1005.4.
  
 22) SEPARATE PERMITS ARE REQUIRED FOR
 ROOFING, ELECTRICAL, MECHANICAL,
 PLUMBING, ETC.
  
 23) THE PLANS ARE REQUIRED TO HAVE THE
 ORIGINAL WET SIGNATURE OF THE ARCHITECT.
 A COPY OR SIGNATURE STAMP IS NOT
 ACCEPTABLE. F.A.C.61G1-16.003
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202