| Plan Review Notes For Permit 02121020 |
| Permit Number |
02121020 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-01-06 00:00:00 | BUILDING DENIED | | | | | | 1) PRODUCT APPROVAL SUBMITTED FOR FRENCH | | | DOOR WITH SIDELITES DOES NOT HAVE | | | IMPACT-RESISTANT GLASS AS INDICATED IN | | | THE HISTORIC PRESERVATION DIVISION | | | APPROVAL. | | | | | | 2) THE PRODUCT APPROVAL FOR THE WINDOWS | | | IS NOT FOR THE YALE OGRON, SERIES 580, | | | THAT ARE SPECIFIED IN THE H.P.D. | | | APPROVAL. | | | | | | 3) THE PRODUCT APPROVALS FOR THE STORM | | | PANELS ARE MISSING THE 9 PAGES OF | | | APPROVED DRAWINGS NO. 00-252. | | | | | | NOTE: IF ANY OF THE BEDROOM WINDOWS ARE | | | BEING REPLACED THE NEW WINDOWS MUST | | | COMPLY WITH THE EMERGENCY EGRESS | | | REQUIREMENTS FOR NET CLEAR OPENINGS PER | | | FLORIDA BUILDING CODE SECTION 1005.4 | | | | | | IF YOU HAVE ANY QUESTIONS CALL : | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)659-8096 EXT.8202 |
|