| 2003-01-06 00:00:00 | ************* UNSAT *************** |
| | |
| | 1)NOTE: PLANS MENTION NEW ELECTRICAL |
| | PANEL IN GARAGE, PLEASE CLARIFY SIZE, |
| | CONDUCTOR CONDUITS ETC. PLEASE SUBMIT |
| | A RISER DIAGRAM. PLEASE ALSO IF CONDUCT- |
| | -ORS ARE OVERHEAD, THEN NO MORETHAN 8' |
| | OF UNPROTECTED CONDUCTORS ARE PERMITTED |
| | "INSIDE" BLDG. PLEASE NOTE, A MAIN WOULD |
| | BE REQ`D OUTSIDE. PLEASE SHOW GROUNDING |
| | ELECTRODE SYSTEM BONDING OF NEW FOOTER |
| | STEEL. ABOVE PER 250-50/215-5/210-70, |
| | 225-31 |
| | |
| | 2)NOTE: PLEASE SUBMIT AIC RATING FOR |
| | ANY NEW SERVICE EQUIPMENT BEING INSTALL- |
| | -ED PER 110-9. |
| | |
| | 3)NOTE: PLEASE CLARIFY NEW OR EXSITING |
| | REQ`D EGRESS LIGHTING FROM KITCHEN TO |
| | REAR OF HOUSE. PER 210-70 |
| | |
| | 4)NOTE:PLEASE CLARFIY NEW OR EXISTING |
| | WASHER/DRYER/WATERHEATER IN GARAGE? |
| | ELECTRIC OR GAS? |
| | |
| | 5)NOTE: PLEASE NOTE, ALL RECEPTS SERVING |
| | KITCHEN COUNTERSPACE ARE TO BE SHOWN AS |
| | GFI/GFI PROTECTED PER 210-8-A-6. |
| | |
| | 6)NOTE: PLEASE LIST NEW CIRCUITS ON |
| | SUBMITTED PANEL SCHEDULE AND NOTE |
| | 210-52D/210-11-C-3 FOR REQ`D BATH #12, |
| | 20A CIRCUIT. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |