Plan Review Notes
Plan Review Notes For Permit 02120897
Permit Number 02120897
Review Stop E
Sequence Number 1
Notes
Date Text
2003-01-06 00:00:00************* UNSAT ***************
  
 1)NOTE: PLANS MENTION NEW ELECTRICAL
 PANEL IN GARAGE, PLEASE CLARIFY SIZE,
 CONDUCTOR CONDUITS ETC. PLEASE SUBMIT
 A RISER DIAGRAM. PLEASE ALSO IF CONDUCT-
 -ORS ARE OVERHEAD, THEN NO MORETHAN 8'
 OF UNPROTECTED CONDUCTORS ARE PERMITTED
 "INSIDE" BLDG. PLEASE NOTE, A MAIN WOULD
 BE REQ`D OUTSIDE. PLEASE SHOW GROUNDING
 ELECTRODE SYSTEM BONDING OF NEW FOOTER
 STEEL. ABOVE PER 250-50/215-5/210-70,
 225-31
  
 2)NOTE: PLEASE SUBMIT AIC RATING FOR
 ANY NEW SERVICE EQUIPMENT BEING INSTALL-
 -ED PER 110-9.
  
 3)NOTE: PLEASE CLARIFY NEW OR EXSITING
 REQ`D EGRESS LIGHTING FROM KITCHEN TO
 REAR OF HOUSE. PER 210-70
  
 4)NOTE:PLEASE CLARFIY NEW OR EXISTING
 WASHER/DRYER/WATERHEATER IN GARAGE?
 ELECTRIC OR GAS?
  
 5)NOTE: PLEASE NOTE, ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE ARE TO BE SHOWN AS
 GFI/GFI PROTECTED PER 210-8-A-6.
  
 6)NOTE: PLEASE LIST NEW CIRCUITS ON
 SUBMITTED PANEL SCHEDULE AND NOTE
 210-52D/210-11-C-3 FOR REQ`D BATH #12,
 20A CIRCUIT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372