| Plan Review Notes For Permit 02120896 |
| Permit Number |
02120896 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2003-05-17 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | SANITARY RISER DIAGRAM DOES NOT MEET | | | CODE REQUIREMENTS. 909.1 ONLY FIXTURES | | | IN THE BATHROOM GROUP SHALL DRAIN INTO | | | THE HORIZONTAL WET VENT. WASH MACHINE | | | SHALL DRAIN DOWNSTREAM OF THE BATHROOM | | | FIXTURES. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|