Plan Review Notes
Plan Review Notes For Permit 02120896
Permit Number 02120896
Review Stop E
Sequence Number 1
Notes
Date Text
2002-12-30 00:00:00************** UNSAT *****************
  
 1)NOTE: PLEASE NOTE, PER FS/FAC PLANS
 ARE REQ`D TO BE SIGNED, DATED AND SEALED
 BY THE ENGINEER OF RECORD.471.025/
  
 2)NOTE: PLEASE NOTE, MISSING GFI FOR
 BATHROOM, MUST BE 20A AND #12.
 210-52D/210-11-C3 PLEASE LIST ON PANEL
 SCHEDULE.
 3)NOTE: PLEASE NOTE MISSING RECEPT
 210-52
  
 4)NOTE: PLEASE NOTE MISSING SD`S INSIDE
 AND OUTSIDE BEDROOM . NFPA-72 8-4.1.2
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  