| Notes |
| Date |
Text |
| 2003-11-04 00:00:00 | ************* UNSAT ******************* | | | | | | PLEASE SEE THE FOLLOWING STATEMENT FOR | | | EXPLANATION OF "F" STATUS. | | | | | | 1)NOTE: PLANS/REVISION DATED 6/20/03 | | | CAME IN FOR REVIEW. PLANS CONTAINED THE | | | TITLE BLOCK FOR THE ENGINEER OF RECORD, | | | HOWEVER THEY WERE NOT SIGNED, DATED AND | | | SEALED BY THE ENGINEER. PER FS 471.025, | | | AND FAC 61G15-23.002 | | | REVISED ELECTRICAL PLAN IS NOW COMING | | | IN DATED 10/15/03. PLEASE SEE THAT | | | THE ORIGINAL REVOF 6/20/03 IS NOW SIGNED | | | AND SEALED, HOWEVER THIS REV DOES NOT | | | CORRELATE WITH NEW REV OF 10/15/03. | | | PANEL "P" ETC. | | | | | | PLEASE TAKE OUT ALL OLD/VOIDED SHEETS, | | | SUBMIT COMPLETE ELECTRICAL REVISIONS TO | | | LAST REVISED SET, HAVE PLANS SIGNED,DATE | | | -D AND SEALED BY THE ORIGINAL ENGINEER | | | OF RECORD(CHANE ENG) AND SUBMIT FOR | | | REVIEW AND STAMPING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|