| 2003-01-23 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | 1) FBC* 104.2.4SITE SURVEY.A SIGNED |
| | AND SEALED SURVEY DRAWING PREPARED BY A |
| | QUALIFIED SURVEYOR IS REQUIRED (REF: |
| | 472.025(1) FL. STATUTES.) |
| | |
| | 2) FBC* 104.1.1DUMPSTER.A SEPARATE |
| | PERMIT APPLICATION WILL BE REQUIRED FOR |
| | THE DETACHED DUMPSTER ENCLOSURE. |
| | |
| | 3) FBC* 104.1.1AWNINGS.A SEPARATE |
| | PERMIT APPLICATION WILL BE REQUIRED FOR |
| | THE INSTALLATION OF THE VINYL AWNINGS. |
| | |
| | 4) FBC T500 AND T600THE PLANS SHALL |
| | STATE WHETHER THE BUILDING IS |
| | SPRINKLERED OR UNSPRINKLERED. |
| | |
| | 5) FBC 704.3TENANT SEPARATION WALLS. |
| | THE PLANS SHALL BE AMENDED TO STATE THE |
| | 1-HOUR FIRE RATING REQUIREMENT FOR THE |
| | TENANT FIRE SEPARATION WALLS AT THE |
| | TOILETS AND 'FUTURE PARTITION' LOCATIONS |
| | |
| | 6) FBC 1027.1.1NUMBER OF EXITS FROM |
| | THE STORAGE LOFT.THE 'LOFT' DOES NOT |
| | MEET THE FBC 503.2.3.2 REQUIREMENTS FOR |
| | A MEZZANINE, AND SO MUST BE CONSIDERED |
| | AS A SECOND STORY.A SINGLE EXIT IS |
| | ONLY PERMITTED IN A STORAGE OCCUPANCY |
| | WITH A MAXIMUM OF ONE STORY.A SECOND |
| | MEANS OF EGRESS IS REQUIRED FROM THE |
| | STORAGE LOFT. |
| | |
| | 7) SHEET 8, SECTION 1.STORAGE LOFT |
| | FLOOR.THE STATED LISTING NUMBER |
| | 'UL 501' DOES NOT APPEAR TO BE A VALID |
| | LISTING.SHOULD THIS BE 'UL# L501'? |
| | AMEND THE PLANS AS NECESSARY. |
| | |
| | 8) SUBMIT A PRODUCT APPROVAL FOR THE |
| | PROPOSED ROOFING. |
| | |
| | 9) ROLL-UP DOOR PRODUCT APPROVAL.THE |
| | DOOR ELEVATIONS ON PLAN SHEET #2, |
| | SPECIFY A 16'-0" WIDE DOOR.THIS WIDTH |
| | APPEARS TO BE OUTSIDE THE SCOPE OF THE |
| | SUBMITTED ROLL-UP DOOR PRODUCT APPROVAL |
| | NOA# 00-0508.1.THE PRODUCT APPROVAL |
| | DRAWING SHEETS ARE NOT COMPLETELY |
| | LEGIBLE BUT THE PLAN VIEW ON SHEET 1 |
| | SHOWS A MAXIMUM DOOR WIDTH WHICH IS LESS |
| | THAN 16'-0".SUBMIT AN APPROPRIATE |
| | PRODUCT APPROVAL OR REVISE THE PLANS |
| | ACCORDINGLY. |
| | |
| | 10) IF NEW PLAN SHEETS ARE REQUIRED, IN |
| | ORDER TO ADDRESS THE ABOVE COMMENTS, THE |
| | OLD SHEETS SHALL BE REMOVED AND THE NEW |
| | SHEETS INSERTED.ONE COPY OF EACH OLD |
| | SHEET SHALL BE INCLUDED WITH THE |
| | RESUBMITTAL FOR COMPARISON OF REVISIONS. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | IF YOU HAVE ANY QUESTIONS PLEASE CALL: |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |