| Plan Review Notes For Permit 02120875 |
| Permit Number |
02120875 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-12-23 00:00:00 | ************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE PROVIDE PANEL SCHEDULE | | | AND LIST THE FOLLOWING CIRCUITS, | | | BATHS, 210-52D/210-11-C3 | | | ARC FAULT 210-12 AND OTHER REQ`D | | | DEDICATED BRANCH CIRCUITS. | | | | | | 2)NOTE: PLEASE SHOW FRONT AND REAR RECEP | | | 210-52E | | | | | | 3)NOTE: PLEASE SHOW EGRESS LTS IN | | | KITCHEN. 210-70 | | | | | | PLEASE SHOW THE ABOVE INFORMATION FOR | | | REVIEW.IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|