| Plan Review Notes For Permit 02120797 |
| Permit Number |
02120797 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-01-06 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION,MAKE ANY NECESSARY CHANGES | | | ON THE PLANS AND RESUBMIT FOR REVIEW. | | | | | | 1} PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 2} PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S). PER 210-11-C-3 | | | MUST BE 20A AND #12AWG. | | | | | | 3} PLEASE LIST THE REQ'D ARC | | | FAULT PROTECTED CIRCUITS ON PANEL | | | SCHEDULE OR NOTE ON PLANS FOR BRANCH | | | CIRCUIT PROTECTION. PER 210-12 | | | | | | 4} CIRCUIT # 18 IS LABELED 15 AMPS AND | | | SMALL APPLIANCE,PLEASE COMPLY WITH | | | 210-52(B). | | | | | | 5} THE COMPUTER ROOM NEEDS ANOTHER | | | RECEPTACLE TO COMPLY WITH 210-52(A)(1). | | | | | | 6} PLEASE INDICATE WHERE THE SERVICE | | | DISCONNECT IS LOCATED. | | | | | | 7} THE HALL SMOKE DETECTOR MUST COMPLY | | | WITH 8-1.4.2 NFPA-72. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT. 8392 |
|