2003-01-06 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE ANY NECESSARY CHANGES
 ON THE PLANS AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 3} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 4} CIRCUIT # 18 IS LABELED 15 AMPS AND
 SMALL APPLIANCE,PLEASE COMPLY WITH
 210-52(B).
  
 5} THE COMPUTER ROOM NEEDS ANOTHER
 RECEPTACLE TO COMPLY WITH 210-52(A)(1).
  
 6} PLEASE INDICATE WHERE THE SERVICE
 DISCONNECT IS LOCATED.
  
 7} THE HALL SMOKE DETECTOR MUST COMPLY
 WITH 8-1.4.2 NFPA-72.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392