Plan Review Notes
Plan Review Notes For Permit 02120794
Permit Number 02120794
Review Stop E
Sequence Number 1
Notes
Date Text
2002-12-23 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE CLARIFY WHERE ELECTRICAL
 FEEDS ARE COMING FROM, CIRCUITING,
 PANEL/SERVICE? ETC.
  
 2)NOTE: PLEASE NOTE, ALL 6 1000W LIGHTS
 ARE SHOWN ON SAME CIRCUIT? PLEASE
 CLARIFY VOLTAGE BEING USED FOR THE
 LOAD ON CIRCUITS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372