| Date |
Text |
| 2004-02-13 00:00:00 | ************** UNSAT **************** |
| | |
| | 1)NOTE: PLEASE SUBMIT TWO SETS OF PLANS |
| | SIGNED, DATED AND SEALED BY THE ARCH |
| | AND ENGINEER OF RECORD. PLEASE SEE |
| | ONE SET IS A COPY OF THE SIGNED AND |
| | SEALED PLANS. PLEASE SEE ONE SET IS |
| | DONE AND SUBMITTED IN PENCIL. PLEASE |
| | NOTE THIS NOT PERMITTED. |
| | PLANS MUST BE REPRINTED. |
| | PLEASE ALSO INCLUDE ALL LICENSE #'S |
| | IN TITLE BLOCK FOR ENGINEER. CERTIFICATE |
| | OF AUTHORIZATION # IS REQUIRED PER |
| | FS 471.023. 61G15-23.002 OF FAC. |
| | ABOVE ALSO PER FS 471.025, 481.221 |
| | |
| | 2)NOTE: PLEASE SEE THAT PLANS ARE NOW |
| | COMING BACK IN AFTER ORIG CORRECTIONS |
| | WERE MADE TO PLANS. RISER IS ONCE |
| | AGAIN INDICATING A 425A SERVICE WITH A |
| | 400A METER CAN. |
| | PLEASE SUBMIT A COMPLETED RISER DIAGRAM |
| | FOR FULL REVIEW. ONE SHEET HAS THE ORIG |
| | RISER CROSSED OUT. THE OTHER SHEET IS |
| | MISSING INFORMATION NEEDED. |
| | PLEASE INCLUDE ALL CONDUCTOR SIZES. |
| | 215.5 |
| | |
| | 3)NOTE: PANEL "C" DOES NOT LIST PANEL |
| | "D". NO OCP.? |
| | |
| | 4)NOTE: PLEASE SHOW AHU KW RATINGS IN |
| | LOAD CALCULATIONS. LOAD CALCS DO NOT |
| | SEEM TO CORRELATE WITH OCP SHOWN ON |
| | PANEL SCHEDULE. |
| | |
| | 5)NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS MIN OF |
| | 20'FROM COOKING APPL. NFPA-72 8-1.4.2 |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| | |
| | 6)NOTE: PLEASE SHOW A/C UNITS ON PLANS, |
| | DISC'S PER 440.11 AND RECEPTS REQ'D PER |
| | 210.63 |
| | |
| | PLEASE SUBMIT TWO COMPLETED SETS FOR |
| | REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |