2003-03-21 00:00:00************** UNSAT *****************
  
 PLEASE SEE FIRST TWO REVIEWS.
 THERE ARE STILL A COUPLE OF NOTES NOT
 DONE.
  
 1)NOTE: PLEASE SUBMIT AIC RATING FOR ALL
 NEW EQUIPMENT. MAINS/PANELS AND BRKRS
 ARE ALL TO BE RATED FOR THE AVAILABLE
 FAULT CURRENT. IT WAS NOTED ON PANEL
 SCHEDULE THAT BRANCH BRKRS ARE TO
 SERIES RATED WHICH IS OK. HOWEVER NOTH-
 -ING WAS SUBMITTED FOR NEW MAIN DISC OR
 PANEL?? 110-9/215-5
  
 2)NOTE: PLEASE SIZE SEC`S PER 310-15.
 PLANS NOW SHOW 250MCM WHICH IS RATED
 FOR A 300A SERVICE PER 310-15. PLANS
 SHOW A 400A SERVICE.
  
 3)NOTE:PLEASE SEE LOAD CALCULATIONS,NOW
 A/C`S HAVE BEEN ADDED BUT LOAD CALCS
 NEED TO BE DONE PER NEC 220.
 PLEASE ALSO NOTE, MAX OCP FOR 5KW CAN
 NOT EXCEED 150% OF LOAD. THE MIN IS 125%
 PER 424-3B
 PLEASE ALSO SEE OCP SHOWN FOR 4.5KW
 WATER HEATER. WH OCP SHOULD BE SET A MIN
 OF 125% OF LOAD AND MAX 150%. PLEASE
 ADJUST.422-13/422-11E
  
 4)NOTE: PLEASE HAVE REVSION DATES SHOWN
 ON RIGHT SIDE OF PLANS, ALL SHOWN AS
 00/00/00?
  
 PLEASE NOTE PREVIOUS NOTES MENTIONED
 FS 553-80(2)(B) WHICH SAYS A 4X FEE
 SHALL BE ADDED FOR PLANS W/ COMMENTS
 ATTACHED AND TURNED DOWN FOR THE SAME
 NOTES 3 OR MORE TIMES. PLEASE SEE LETTER
 ATTACHED. PLEASE CALL TO SET UP A TIME
 TO GO OVER PLANS AND IF BEFORE RESUB-
 -MITTING PLANS A MEETING IS DESIRED TO
 OVER PLANS, PLEASE CALL.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372