| 2003-03-21 00:00:00 | ************** UNSAT ***************** |
| | |
| | PLEASE SEE FIRST TWO REVIEWS. |
| | THERE ARE STILL A COUPLE OF NOTES NOT |
| | DONE. |
| | |
| | 1)NOTE: PLEASE SUBMIT AIC RATING FOR ALL |
| | NEW EQUIPMENT. MAINS/PANELS AND BRKRS |
| | ARE ALL TO BE RATED FOR THE AVAILABLE |
| | FAULT CURRENT. IT WAS NOTED ON PANEL |
| | SCHEDULE THAT BRANCH BRKRS ARE TO |
| | SERIES RATED WHICH IS OK. HOWEVER NOTH- |
| | -ING WAS SUBMITTED FOR NEW MAIN DISC OR |
| | PANEL?? 110-9/215-5 |
| | |
| | 2)NOTE: PLEASE SIZE SEC`S PER 310-15. |
| | PLANS NOW SHOW 250MCM WHICH IS RATED |
| | FOR A 300A SERVICE PER 310-15. PLANS |
| | SHOW A 400A SERVICE. |
| | |
| | 3)NOTE:PLEASE SEE LOAD CALCULATIONS,NOW |
| | A/C`S HAVE BEEN ADDED BUT LOAD CALCS |
| | NEED TO BE DONE PER NEC 220. |
| | PLEASE ALSO NOTE, MAX OCP FOR 5KW CAN |
| | NOT EXCEED 150% OF LOAD. THE MIN IS 125% |
| | PER 424-3B |
| | PLEASE ALSO SEE OCP SHOWN FOR 4.5KW |
| | WATER HEATER. WH OCP SHOULD BE SET A MIN |
| | OF 125% OF LOAD AND MAX 150%. PLEASE |
| | ADJUST.422-13/422-11E |
| | |
| | 4)NOTE: PLEASE HAVE REVSION DATES SHOWN |
| | ON RIGHT SIDE OF PLANS, ALL SHOWN AS |
| | 00/00/00? |
| | |
| | PLEASE NOTE PREVIOUS NOTES MENTIONED |
| | FS 553-80(2)(B) WHICH SAYS A 4X FEE |
| | SHALL BE ADDED FOR PLANS W/ COMMENTS |
| | ATTACHED AND TURNED DOWN FOR THE SAME |
| | NOTES 3 OR MORE TIMES. PLEASE SEE LETTER |
| | ATTACHED. PLEASE CALL TO SET UP A TIME |
| | TO GO OVER PLANS AND IF BEFORE RESUB- |
| | -MITTING PLANS A MEETING IS DESIRED TO |
| | OVER PLANS, PLEASE CALL. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |