| Plan Review Notes For Permit 02120658 |
| Permit Number |
02120658 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-02-24 00:00:00 | ************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE SEE RISER, PLANS NOW | | | SHOW A 425A SERVICE ON A 400A METERCAN. | | | PLEASE CORRELATE SERVICE SIZE WITH | | | EQUIPMENT. | | | | | | 2)NOTE: PLEASE SHOW SERVICE ENTRANCE | | | CONDUCTOR SIZES FROM METER TO GUTTER AND | | | ON TO 225A, SHOWS 2/0`S FOR 200A. | | | 310-15/240-3 | | | | | | 3)NOTE: PLEASE SEE PLANS, SHOW THREE | | | A/C SYSTEMS AND ONLY ONE SHOWN ON LOAD | | | CALCULATIONS,??? | | | | | | 4)NOTE: PLEASE SEE NOTES FROM FIRST | | | REVIEW. PLEASE SEE THAT MOST OF THE NOTE | | | -S FROM FIRST REVIEW ARE THE SAME AND | | | HAVE NOT BEEN ADDRESSED. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. PLEASE ALSO SEE LETTER ATTACHED | | | PER FS 553.80(2) (B). IF THERE ARE ANY | | | QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|