| Date |
Text |
| 2003-03-03 00:00:00 | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 02120658 |
| | ADD: 6815 S FLAGLER DR |
| | CONT: HINKLEY CONSTRUCTION |
| | TEL: (561)832-3310 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 1) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | ADDRESS ON CURRENT NOC NOT CORRECT. |
| | |
| | 2) PROVIDE FLOOD ZONE ELEVATION |
| | CERTIFICATE FOR NEW CONSTRUTION WITH |
| | BASE FLOOD ELEVATION, CITY CODE REQUIRES |
| | AN ADDITIONAL 6". THE ADDITION IS |
| | LOCATED IN A A5 FLOOD ZONE, MINIMUM |
| | FLOOR ELEVATION IS 7'-6" THE NGVD GIVEN |
| | FOR ORIGINAL HOUSE IS 5.67 + 1.75 FINISH |
| | FLOOR ELEVATION IS 7'-51/4" NOT 7'-6". |
| | |
| | 3) PREVIOUS COMMENT #(8) : |
| | 1606.1.4(1) IN WIND BORNE DEBRIS |
| | REGIONS, EXTERIOR GLAZING THAT RECEIVES |
| | POSITIVE PRESSURE IN BUILDINGS SHALL BE |
| | ASSUMED TO BE OPENINGS UNLESS SUCH |
| | GLAZING IS IMPACT RESISTANT OR PROTECTED |
| | WITH AN IMPACT RESISTANT COVERING MEET- |
| | ING THE REQUIREMENTS OF SSTD 12, ASTM |
| | E 1886 AND ASTM E 1996 OR MIAMI-DADE. |
| | |
| | 1) GLAZED OPENINGS LOCATED WITHIN 30 FT |
| | OF GRADE SHALL MEET THE REQUIREMENTS OF |
| | LARGE MISSLE TEST. |
| | FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORT, SBCCI OR DADE COUNTY |
| | REPORT ARE ACCEPTED. MISSING REPORTS: |
| | A) FIXED WINDOWS ABOVE CASEMENT WINDOWS |
| | B) MULLIONS HORIZONTAL / VERTICAL |
| | C) SWING DOORS W/ SIDELIGHTS |
| | D) ROOFING ASSEMBLIES |
| | |
| | 4)1707.4.5.1 MULLIONS OCCURRING |
| | BETWEEN INDIVIDUAL WINDOW AND GLASS |
| | DOOR ASSEMBLIES. TESTING REPORTS ARE |
| | REQUIRED BY AN APPROVED TESTING |
| | LABORATORY OR BE ENGINEERED. |
| | |
| | 5)1707.4.5.2 MULLIONS SHALL BE DESIGN- |
| | ED TO TRANSFER THE DESIGN PRESSURE LOADS |
| | APPLIED BY THE WINDOW OR DOOR ASSEMBLIES |
| | TO THE ROUGH OPENING SUBTRATE. |
| | |
| | 6)2804.4.1 FACTORY-BUILT CHIMNEYS |
| | FACTORY BUILT CHIMNEYS SHALL BE LISTED |
| | AND SHALL BE INSTALLED IN ACCORDANCE |
| | WITH THE CONDITIONS OF THE LISTING, AND |
| | MANUFACTURER'S INSTRUCTION. |
| | |
| | 7)2804.4.4. FACTORY-BUILT CHIMNEYS |
| | FOR USE WITH CLOSED COMBUSTION WOOD |
| | BURNING APPLIANCES SHALL COMPLY WITH |
| | THE TYPE HT REQUIREMENT UL 103. |
| | |
| | 8)CHIMNEYS FOR THE USE WITH FACTORY- |
| | BUILT FIREPLACES SHALL MEET THE |
| | REQUIREMENTS OF UL 127. |
| | |
| | 9)2806.1.2 FACTORY BUILT FIREPLACES |
| | SHALL BE TESTED IN ACCORDANCE WITH AND |
| | MEET THE REQUIREMENTS OF UL 127. |
| | |
| | 10)2810 FRESH AIR INTAKES, FRESH AIR |
| | INTAKESSHALL BE SCREENED WITH A CORRO- |
| | SION RESITANT MATERIAL NOT LARGER THAN |
| | 1/2 INCH MESH. FRESH AIR INTAKES SHALL |
| | NOT BE TAKEN FROM A LOCATION CLOSER THAN |
| | 10 FT FROM ANY CHIMNEY OR VENT OUTLET OR |
| | SANITARY SEWER VENT OUTLET, UNLESS SUCH |
| | VENT IS NOT LESS THAN 24" ABOVE THE |
| | FRESH AIR VENT. FRESH AIR INTAKE VENTS |
| | LOCATED ON THE ROOFS WILL BE PROPERLY |
| | MARKED WITH A UNIVERSAL MARKING, |
| | ***"INTAKE"***, PERMANETLY ATTACHED. |
| | SEE 705.1.1.4 FOR FIRE PROTECTION. |
| | |
| | COMMENT: NOTES ON MECH PLANS. |
| | WE ARE LOOKING FOR THE MANUFACTURERS |
| | SPEC/ INSTALLATION GUIDE. |
| | |
| | 11)BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | JIM WITMER |
| | BUILDING PLAN REVIEW |
| | TEL: (561)659-8096 X 8412 |
| | FAX: (561)659-8026 |