Plan Review Notes
Plan Review Notes For Permit 02120658
Permit Number 02120658
Review Stop E
Sequence Number 1
Notes
Date Text
2003-01-30 00:00:00************* UNSAT *****************
  
 1)NOTE: PLEASE CLARIFY LOCATION OF NEW
 PANEL? PLANS SHOW A NEW PANEL IN KITCHEN
 , PLEASE CLARIFY IF THIS THE SAME PANEL
 SHOWN ON RISER. IF SO, PLEASE SEE 230-72
 FOR GROUPING OF MAINS.
  
 2)NOTE: PLEASE SUBMIT AIC RATING(S) FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 ALL MAINS, PANELS, BRKRS ARE TO BE
 RATED FOR THE AVAILABLE FULAT CURRENT.
 110-9
  
 3)NOTE: PLEASE NOTE/CLARIFY SIZE OF
 EXISTING SERVICE ENTRANCE CONDUCTORS.
  
 4)NOTE: PLEASE PROVIDE A PANEL SCHEDULE
 AND SHOW ALL NEW ITEMS W/ WIRE AND OCP
 SIZES.
 PLEASE SHOW WIRING AND SIZES FOR AHU`S/
 CU`S.
  
 5)NOTE: PLEASE LIST THE REQ`D BATH(S)
 DEDICATED CIRCUIT(S) PER 210-52D,210-11-
 C-3.
  
 6)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 CIRCUITS FOR BEDROOM/SLEEPING ROOMS
 PER 210-12
  
 7)NOTE: MISSING SD`S REQ`D INSIDE AND
 OUTSIDE ALL SLEEPING ROOMS. NFPA-72
 8-1. ALSO ON EACH LEVEL OF A MULTI-LEVEL
 HOUSE.
 8)NOTE: PLEASE SHOW ALL KITCHEN COUNTER-
 -SPACE OUTLETS AS GFI/GFI PROTECTED PER
 210-8-A-6.
  
 9)NOTE: PLEAS CLARIFY LOAD SHOWN FOR
 WATER HEATER (1). SHOWN AS 9KW? 40A OCP,
 PLEASE SEE NEC 422-13
  
 10)NOTE: PLEASE SHOW A/C UNITS ON
 ELECTRICAL PLANS AND SHOW DISC`S PER
 440-11.
  
 11)NOTE: PLEASE SEE MISSING OUTLET(S)
 PER 210-52, MASTER BEDROOM.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372