| 2003-01-30 00:00:00 | ************* UNSAT ***************** |
| | |
| | 1)NOTE: PLEASE CLARIFY LOCATION OF NEW |
| | PANEL? PLANS SHOW A NEW PANEL IN KITCHEN |
| | , PLEASE CLARIFY IF THIS THE SAME PANEL |
| | SHOWN ON RISER. IF SO, PLEASE SEE 230-72 |
| | FOR GROUPING OF MAINS. |
| | |
| | 2)NOTE: PLEASE SUBMIT AIC RATING(S) FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | ALL MAINS, PANELS, BRKRS ARE TO BE |
| | RATED FOR THE AVAILABLE FULAT CURRENT. |
| | 110-9 |
| | |
| | 3)NOTE: PLEASE NOTE/CLARIFY SIZE OF |
| | EXISTING SERVICE ENTRANCE CONDUCTORS. |
| | |
| | 4)NOTE: PLEASE PROVIDE A PANEL SCHEDULE |
| | AND SHOW ALL NEW ITEMS W/ WIRE AND OCP |
| | SIZES. |
| | PLEASE SHOW WIRING AND SIZES FOR AHU`S/ |
| | CU`S. |
| | |
| | 5)NOTE: PLEASE LIST THE REQ`D BATH(S) |
| | DEDICATED CIRCUIT(S) PER 210-52D,210-11- |
| | C-3. |
| | |
| | 6)NOTE: PLEASE LIST THE REQ`D ARC FAULT |
| | CIRCUITS FOR BEDROOM/SLEEPING ROOMS |
| | PER 210-12 |
| | |
| | 7)NOTE: MISSING SD`S REQ`D INSIDE AND |
| | OUTSIDE ALL SLEEPING ROOMS. NFPA-72 |
| | 8-1. ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| | HOUSE. |
| | 8)NOTE: PLEASE SHOW ALL KITCHEN COUNTER- |
| | -SPACE OUTLETS AS GFI/GFI PROTECTED PER |
| | 210-8-A-6. |
| | |
| | 9)NOTE: PLEAS CLARIFY LOAD SHOWN FOR |
| | WATER HEATER (1). SHOWN AS 9KW? 40A OCP, |
| | PLEASE SEE NEC 422-13 |
| | |
| | 10)NOTE: PLEASE SHOW A/C UNITS ON |
| | ELECTRICAL PLANS AND SHOW DISC`S PER |
| | 440-11. |
| | |
| | 11)NOTE: PLEASE SEE MISSING OUTLET(S) |
| | PER 210-52, MASTER BEDROOM. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |