Plan Review Notes
Plan Review Notes For Permit 02120658
Permit Number 02120658
Review Stop B
Sequence Number 1
Notes
Date Text
2003-02-04 00:00:00BUILDING PLAN REVIEW
 PERMIT: 02120658
 ADD: 101 ALPINE ROAD
 CONT: HINCKLY CONSTRUCTION
 TEL: (561)832-3310
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) THE RECORDED PROPERTY ADDRESS IS
 101 ALPINE RD. DOES THE OWNER WANT TO DO
 A ADDRESS CHANGE TO 6815 S FLAGLER? IF
 SO THEY SHOULD WRITE A LETTER FOR AN ADD
 RESS CHANGE, WE WILL REARCH THE PROPOSED
 ADDRESS TO SEE IF IT IS AVAILABLE AND
 NOTIFY ALL AGENCIES OF THE CHANGE.
  
 2) NOTICE OF COMMENCEMENT IS UNDER 101
 ALPINE ROAD IF THE ADDRESS IS TO BE
 CHANGED.
  
 3) PROVIDE FLOOD ZONE ELEVATION
 CERTIFICATE FOR NEW CONSTRUTION WITH
 BASE FLOOD ELEVATION, CITY CODE REQUIRES
 AN ADDITIONAL 6". THE ADDITION IS
 LOCATED IN A A5 FLOOD ZONE MINIMUM FLOOR
 ELEVATION IS 7'-6''. INDICATE WHAT THE
 FLOOR ELEVATION IS NOT IN REFRENCE TO
 EXISTING FLOOR ELEVATION.
  
 4) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 PROVIDE SOIL BORING TEST INDICATING
 WHAT THE MINIMUM BEARING CAPACITY IS?
  
 5)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 STRUCTURAL PLANS INDICATE THE USE OF A
 PRECAST SLAB SYSTEM "AUREA SLAB", PRO-
 VIDE ADDITIONAL INFORMATION, COULD NOT
 FIND ANYTHING ON ENTERNET?
  
 6) S-3 INDICATES THE MEAN ROOF HEIGHT
 OF 30'-0". THIS IS FROM THE EXISTING
 FLOOR LEVEL OF EXISTING RESIDENCE.
 WHAT IS IT FROM NGVD?
  
 7) TRUSS ANCHOR SCHEDULE ANCHOR D,E&F
 USE A USP2 WHICH IS A WOOD TO WOOD
 ANCHOR, PLANS INDICATE THAT IT IS A
 EMBEDDED ANCHOR?
  
 8)1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
 1) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED.MISSING REPORTS:
 A) FIXED WINDOWS
 B) CASEMENT WINDOWS
 C) MULLIONS
 D) SWING DOORS
 E) SWING DOORS W/ SIDELIGHTS
 F) ROOFING ASSEMBLIES
 G) STORM SHUTTERS
  
 9)1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 10) 1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 11)1707.4.3 EACH EXTERIOR DOOR
 ASSEMBLY NOT COVERED BY 1707.4.2
 (GLAZED DOORS) SHALL BE LISTED AND TEST-
 ED FOR A PERIOD EQUAL TO THE QUANITY
 3600/ V WHERE THE TIME PERIOD IS IN
 SECTIONS AND V IS IN MILES PER HR TAKEN
 FROM FIGURE 1606. THE TIME PERIOD SHALL
 ALSO INCLUDE A 10 SECOND PERIOD AT A
 LOAD EQUAL TO 1.5 TIMES THE DESIGN
 PRESSURE. DADE COUNTY & SBCCI REPORTS
 ARE ACCEPTED.
  
 12) 1707.4.4.1 ANCHOR REQUIREMENTS:
 WINDOW & DOOR ASSEMBLIES SHALL BE ANCHOR
 ED IN ACCORDANCE WITH THE PUBLISHED
 MANUFACTURER'S RECOMMENDATIONS TO
 ACHIEVE THEDESIGN PRESSURE SPECIFIED.
 SUBSTITUTE ANCHORING SYSTEM USED FOR
 THE SUBSTRATE NOT SPECIFIED BY THE
 FENESTRATION MANUFACTURER SHALL PROVIDE
 EQUAL OR GREATER ANCHORING AS DEMONSTRA-
 TED BY ACCEPTED ENGINEERING PRACTICES.
  
 13)PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
  
 14)FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 15) 1816.1.6. SOILS TREATMENT SHALL BE
 REQUIRED UNDER ALL EXTERIOR CONCRETE
 ON GRADE WITHIN 1 FOOT OF THE PRIMARY
 STRUCTURE SIDEWALLS. SHEET A2 & A7 INDI-
 CATE THERE ARE VARIOUS SLABS NEXT TO
 THE STRUCTUE.
  
 16)2804.4.1 FACTORY-BUILT CHIMNEYS
 FACTORY BUILT CHIMNEYS SHALL BE LISTED
 AND SHALL BE INSTALLED IN ACCORDANCE
 WITH THE CONDITIONS OF THE LISTING, AND
 MANUFACTURER'S INSTRUCTION.
  
 17)2804.4.4. FACTORY-BUILT CHIMNEYS
 FOR USE WITH CLOSED COMBUSTION WOOD
 BURNING APPLIANCES SHALL COMPLY WITH
 THE TYPE HT REQUIREMENT UL 103.
  
 18)CHIMNEYS FOR THE USE WITH FACTORY-
 BUILT FIREPLACES SHALL MEET THE
 REQUIREMENTS OF UL 127.
  
 19)2806.1.2 FACTORY BUILT FIREPLACES
 SHALL BE TESTED IN ACCORDANCE WITH AND
 MEET THE REQUIREMENTS OF UL 127.
  
 20)2810 FRESH AIR INTAKES, FRESH AIR
 INTAKESSHALL BE SCREENED WITH A CORRO-
 SION RESITANT MATERIAL NOT LARGER THAN
 1/2 INCH MESH. FRESH AIR INTAKES SHALL
 NOT BE TAKEN FROM A LOCATION CLOSER THAN
 10 FT FROM ANY CHIMNEY OR VENT OUTLET OR
 SANITARY SEWER VENT OUTLET, UNLESS SUCH
 VENT IS NOT LESS THAN 24" ABOVE THE
 FRESH AIR VENT. FRESH AIR INTAKE VENTS
 LOCATED ON THE ROOFS WILL BE PROPERLY
 MARKED WITH A UNIVERSAL MARKING,
 ***"INTAKE"***, PERMANETLY ATTACHED.
 SEE 705.1.1.4 FOR FIRE PROTECTION.
  
 21) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 PROVIDE MANUFACTURERS SPEC FOR PRIVATE
 (RESIDENTIAL) ELEVATOR.
  
 22) 1007.5.3 HANDRAILS: STAIRS LEADING
 FROM THE COVERED TERRACE MAY HAVE A
 GUARDRAIL BUT NO HANDRAIL MEETING THIS
 SECTION.
  
 23) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 MISSING INFORMATION ON HOW THE CHIMNEY
 WILL FRAME INTO THE ROOF FRAMING?
  
 24) SHEET A-7 SECTION 2, SECOND FLOOR
 TERRACE, WHAT TYPE OF MATERIAL IS TO BE
 USED TO STOP RAIN FROM PENETRATING THE
 SLAB INTO THE INTERIOR? STRUCTURAL
 DETAILS S2 DETAIL OF DECK 11/S5 MISSING?
  
 25)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved