| Date |
Text |
| 2003-03-07 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | |
| | 1) SHT P201 SECTI0ON 909.1 - WET VENT, |
| | ONLY FIXTURES WITHIN THE BATHROOM GROUP |
| | SHALL CONNEDT TO THE WET VENTED HORIZON- |
| | TAL BRANCH DRAIN. ANY ADDITIONAL FIX- |
| | TURES SHALL DISCHARGE DOWNSTREAM OF THE |
| | WET VENT. - SEE ALL UNITS |
| | 2) SHT P2.01 PIPE SIZING MISSING FOR |
| | SOME STORM BLDG. DRAIN BRANCHES. PIPE |
| | SIZE NOT SUFFICIENT BY UNIT 27L. 6" PIPE |
| | WITH 11,000 SQ FT. |
| | 3) SHT P2.01 SECTION 504.7.1, THE DIS- |
| | CHARGE PIPE SHALL NOT HAVE ANY TRAPPED |
| | SECTIONS. (SAME FOR ALL SHEETS) |
| | 4) CONDENSATE SIZING. PLEASE SUBMIT FLOW |
| | CALCULATIONS FOR CONDENSATE TO CHECK |
| | SIZING OF CONDENSATE LINES. |
| | 5) SHT P2.01 FIRST FLOOR UNITS 15L, 17L, |
| | 18L, & 19L. SHOW WHERE BRANCH LINES TO |
| | THESE UNITS TIE INTO BLDG. DRAIN. ALSO |
| | IT APPEARS THAT THE FIXTURE UNITS ARE |
| | NOT ADDED TO ACCUMULATIVE TOTAL. |
| | 6) SHT P2.04 UNITS 9L, 10L, 11L, 12L, & |
| | 14L (SAME COMMENT AS #5 ABOVE) |
| | 7) SHTS P2.01 & P2.04 AREA OF TRENCH |
| | DRAINS NOT INCLUDED ON PLANS. PLEASE |
| | INDICATE AREA BEING DRAIN BY TRENCH |
| | DRAINS. |
| | |