2003-02-07 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) ANSWER NOTED CONCERNING THE 20%
 DISPROPORTIONAL COST FOR ACCESSIBILITY.
 PLEASE ITEMISE ALL ACCESSIBILITY IMPROV-
 MENTS AND SHOW COST OF EACH TO DETERMINE
 HOW MUCH OF THE CONTRACT WAS SPENT FOR
 THESE ITEMS.
 2) FROM PERVIOUS REVIEW: SHT P-2 WATER
 HEATER DETAIL. THERMAL EXPANSION CONTROL
 IS NOT ACHEIVED WITH A HEAT TRAP. EXPAN-
 SION CONTROL REQUIRED BY SECTION 607.3.2
 IS ACCOMPLISHED WITH AN EXPANSION TANK.
 PLEASE CHANGE DETAIL.
  
 REVIEW BY KEN STEVENS