Plan Review Notes
Plan Review Notes For Permit 02120612
Permit Number 02120612
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-12-19 00:00:001) DUCT SMOKE DETECTORS ARE REQUIRED
 TO ACTIVATE THE FIRE ALARM SYSTEM. IN
 THE FIRE ALARM NOTES SECTION, IT
 INDICATES A SUPERVISORY SIGNAL WILL
 BE PROVIDED.
  
 2) IT APPEARS THAT MAGNETIC LOCKS
 ARE PRESENT ON EXIT DOORS. LOCKS ON
 EGRESS DOORS SHALL COMPLY WITH
 DELAYED EGRESS OR ACCESS CONTROLLED.
 PLEASE REVIEW SPECIAL LOCKING
 ARRANGEMENTS IN CHAPTER SEVEN OF THE
 2000 EDITION OF THE LIFE SAFETY CODE.
  
 3) ALL ELECTRICAL, MECHANICAL, AND
 STORAGE ROOM DOORS ARE TO BE FIRE
 SEPARATED FROM OTHER AREAS OF THE
 BUILDING BY AT LEAST ONE HOUR WITH
 RATED OPENING PROTECTIVE DEVICES.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910