2002-12-27 00:00:00*************** UNSAT *****************
  
  
 PLEASE NOTE, ALL ELECTRICAL SHEETS WERE
 STAMPED IN ERROR. PLEASE ADDRESS THE
 FOLLOWING COMMENTS AND SUBMIT NEW SHEETS
 IN SETS WHEN ALL REVIEWS ARE COMPLETE
 AND PLANS ARE RESUBMITTED FOR REVIEW.
  
 1)NOTE: PLEASE NOTE CIRCUITING FOR ALL
 EMERGENCY AND EXITS LTS TO MEET 700-12
 WHICH WILL HAVE AN EFFECT ON LOADING
 OF CIRCUITS, CIRCUIT #`S AND PANEL
 SCHEDULES.
  
 2)NOTE: PLEASE SEE FIRE REVIEW COMMENST
 AS PANELS MAY CHANGE LOCATION DUE TO
 FIRE RATING OF ROOMS WHERE PANELS ARE
 LOCATED.
  
 3)NOTE: PLEASE CLARIFY FIXTURES/TYPES
 IN ORDER TO MEET 700-16
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  