| Plan Review Notes For Permit 02120517 |
| Permit Number |
02120517 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-02-06 00:00:00 | ************* UNSAT ****************** | | | | | | PLEASE SEE NOTES FROM FIRST REVIEW, | | | A FEW RECEPTS WERE ADDED FOR KITCHEN- | | | -COUNTERSPACE. NO OTHER NOTES WERE | | | ADDRESSED. | | | | | | 1)NOTE: PLEASE SEE MISSING EQUIPMENT | | | GROUNDING CONDUCTOR BETWEEN MAIN DISC | | | AND PANEL. PLEASE SIZE PER 250-122. | | | 250-24 | | | | | | 2)NOTE: PLEASE SEE REDLINED PLANS FOR | | | RECEPTS MISSING PER 210-52. | | | | | | PLEASE BE SURE TO TAKE OUT OLD SHEETS | | | AND INSERT NEW SHEETS INTO SETS. | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|