| Plan Review Notes For Permit 02120463 |
| Permit Number |
02120463 |
|
| Review Stop |
E |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2006-05-18 00:00:00 | DENIED | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} IF THE CUT OF THE KITCHEN SUBMITTED | | | PREVIOUSLY (3/15/06) IS TO BE REVIEWED | | | WITHTHIS REVISION, PLEASE SIGN SAME PER | | | 104.2.1 FBC. ALSO INDICATE GFI'S PER | | | 210.8(A)(6)ON THE PLAN. THE ADDRESS IS | | | WRONG ON THAT SHEET STILL. | | | | | | 2} ALL 15 AMP BREAKERS ON THE PANEL | | | SCHEDULE ARE FEEDING # 16 WIRE. | | | SEE310.16 FOR CORRECT CONDUCTOR SIZES | | | FOR OCP. | | | | | | THIS REVISION IS NOT A SUBMITTAL AND HAS | | | A FEE DUE. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | | | | | | | |
|