| Date |
Text |
| 2006-03-23 00:00:00 | ************* UNSAT ************* |
| | |
| | ** PLEASE SEE SOME NOTES NEED TO BE |
| | CORRECTED AND ALSO SEE BELOW FROM REVIEW |
| | DATED ON 10/8/03 WHICH WERE NEVER |
| | SUBMITTED FOR INFORMATION REQUIRED. |
| | PLEASE KNOW, NO FURTHER ELECTRICAL |
| | REVISIONS CAN BE DONE UNTIL ALL MIN FROM |
| | OCT 2003 AND RECENT REV'S ARE SUBMITTED. |
| | |
| | |
| | 1)NOTE: PLEASE SEE ADDRESSING ON PLANS |
| | SHALL CORRELATE WITH APPLICATION AND OUR |
| | SYSTEM IN WHICH THE PERMIT WAS PULLED. |
| | THIS ADDRESS IS FOR 712, NOT 710 WHICH |
| | IS NOT WHAT THIS PERMIT WAS PULLED FOR. |
| | |
| | 2)NOTE: PLEASE CORRELATE KITCHEN PLANS |
| | SUBMITTED. ONLY ONE LAYOUT IS NEEDED FOR |
| | CODE COMPLIANCE. |
| | |
| | |
| | 3)NOTE: PLEASE SEE 210.52C1 FOR SPACING. |
| | |
| | 4) NOTE: PLEASE SEE 210.8A6, AS ALL |
| | COUNTER SPACE RECEPTS IN KITCHENS SHALL |
| | BE SHOWN AS GFI/ GFI PROTECTED. IF ANY |
| | RECEPTS ARE DEDICATED (IE:) MICRO, DISP |
| | ETC, PLEASE IDENTIFY. |
| | |
| | 5)NOTE: PLEASE SEE PLANS MENTIONS DRAWN |
| | BY AND CONTAINS THE PRINTED NAME, |
| | HOWEVER PLANS ARE ALSO REQUIRED TO BE |
| | SIGNED BY THAT PERSON. |
| | FBC ADMIN SECTION 104.2.1 |
| | |
| | 6)NOTE: PLEASE SEE SOME ROOMS WHERE THE |
| | PLANS INDICATE THE ENTIRE RECEPT BEING |
| | SWITCH. PLEASE KNOW, THIS IS ONLY |
| | PERMITTED IF AN ADDITIONAL RECEPT MEETS |
| | 210.52. IF INDEED THESE ARE 1/2 SWITCH? |
| | PLEASE INDICATE. |
| | |
| | 7) NOTE: PLEASE SEE NEC 210.12, PLANS |
| | INDICATE ARC FAULT FOR RECEPTS, WHICH IS |
| | OK AS THESE PLANS ORIGINALLY CAME IN |
| | UNDERTHE PREVIOUS REQUIREMENTS FOR |
| | AFCI PROTECTION, HOWEVER PLEASE SEE |
| | PLANS LENDS TO THE RECEPTS BEING PART OF |
| | THE LIGHTING CIRCUITS, WHICH WOULD THEN |
| | REQUIRE AFCI PROTECTION. PLEASE SEE RMS |
| | ARE BEING SHOWN WITH A SWITCHED LT |
| | FIXTIURE (NO FANS) AND SWITCHED RECEPTS. |
| | WHEN PANEL SCHEDULE AS REQUIRED IS |
| | SUBMITTED, THIS WILL BE VERIFIED. PLEASE |
| | SEE NOTES BELOW. |
| | |
| | ** NOTES FROM 10/8/03** |
| | |
| | ************ NOTES REDLINED ******* |
| | |
| | PANELSCHEDULE WITH ALL OCP SIZES AND |
| | WIRE SIZES TO BE REVISED AND SUBMITTED |
| | BEFORE FINAL. |
| | SEE 250.32 FOR GROUNDING AT TWO OR MORE |
| | BDLGS. |
| | PLEASE SUBMIT ALL OTHER REVISIONS BEFORE |
| | ROUGH, AS STAMPED ON PLANS. |
| | |
| | IF THERE ARE ANY QUESTIONS, PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | **************************************** |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |