Plan Review Notes
Plan Review Notes For Permit 02120463
Permit Number 02120463
Review Stop E
Sequence Number 4
Notes
Date Text
2006-03-23 00:00:00************* UNSAT *************
  
 ** PLEASE SEE SOME NOTES NEED TO BE
 CORRECTED AND ALSO SEE BELOW FROM REVIEW
 DATED ON 10/8/03 WHICH WERE NEVER
 SUBMITTED FOR INFORMATION REQUIRED.
 PLEASE KNOW, NO FURTHER ELECTRICAL
 REVISIONS CAN BE DONE UNTIL ALL MIN FROM
 OCT 2003 AND RECENT REV'S ARE SUBMITTED.
  
  
 1)NOTE: PLEASE SEE ADDRESSING ON PLANS
 SHALL CORRELATE WITH APPLICATION AND OUR
 SYSTEM IN WHICH THE PERMIT WAS PULLED.
 THIS ADDRESS IS FOR 712, NOT 710 WHICH
 IS NOT WHAT THIS PERMIT WAS PULLED FOR.
  
 2)NOTE: PLEASE CORRELATE KITCHEN PLANS
 SUBMITTED. ONLY ONE LAYOUT IS NEEDED FOR
 CODE COMPLIANCE.
  
  
 3)NOTE: PLEASE SEE 210.52C1 FOR SPACING.
  
 4) NOTE: PLEASE SEE 210.8A6, AS ALL
 COUNTER SPACE RECEPTS IN KITCHENS SHALL
 BE SHOWN AS GFI/ GFI PROTECTED. IF ANY
 RECEPTS ARE DEDICATED (IE:) MICRO, DISP
 ETC, PLEASE IDENTIFY.
  
 5)NOTE: PLEASE SEE PLANS MENTIONS DRAWN
 BY AND CONTAINS THE PRINTED NAME,
 HOWEVER PLANS ARE ALSO REQUIRED TO BE
 SIGNED BY THAT PERSON.
 FBC ADMIN SECTION 104.2.1
  
 6)NOTE: PLEASE SEE SOME ROOMS WHERE THE
 PLANS INDICATE THE ENTIRE RECEPT BEING
 SWITCH. PLEASE KNOW, THIS IS ONLY
 PERMITTED IF AN ADDITIONAL RECEPT MEETS
 210.52. IF INDEED THESE ARE 1/2 SWITCH?
 PLEASE INDICATE.
  
 7) NOTE: PLEASE SEE NEC 210.12, PLANS
 INDICATE ARC FAULT FOR RECEPTS, WHICH IS
 OK AS THESE PLANS ORIGINALLY CAME IN
 UNDERTHE PREVIOUS REQUIREMENTS FOR
 AFCI PROTECTION, HOWEVER PLEASE SEE
 PLANS LENDS TO THE RECEPTS BEING PART OF
 THE LIGHTING CIRCUITS, WHICH WOULD THEN
 REQUIRE AFCI PROTECTION. PLEASE SEE RMS
 ARE BEING SHOWN WITH A SWITCHED LT
 FIXTIURE (NO FANS) AND SWITCHED RECEPTS.
 WHEN PANEL SCHEDULE AS REQUIRED IS
 SUBMITTED, THIS WILL BE VERIFIED. PLEASE
 SEE NOTES BELOW.
  
 ** NOTES FROM 10/8/03**
  
 ************ NOTES REDLINED *******
  
 PANELSCHEDULE WITH ALL OCP SIZES AND
 WIRE SIZES TO BE REVISED AND SUBMITTED
 BEFORE FINAL.
 SEE 250.32 FOR GROUNDING AT TWO OR MORE
 BDLGS.
 PLEASE SUBMIT ALL OTHER REVISIONS BEFORE
 ROUGH, AS STAMPED ON PLANS.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
 ****************************************
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved