| 2003-09-15 00:00:00 | ************* UNSAT ****************** |
| | |
| | 1)NOTE: PLEASE SEE THAT ORIG PERMIT |
| | APPLICATION DID NOT COME BACK IN W/ |
| | PACKAGE. PLEASE SUBMIT PERMIT APPL. |
| | PLEASE ALSO SEE THAT PLANS ARE STILL |
| | SHOWING 710 PARK PL??? PERMIT APPL AND |
| | PROPERTY ID USED IS FOR 712 PK PL?? |
| | PLEASE SEE THAT WORK WAS ALREADY DONE ON |
| | 712 ON PREVIOUS PERMITS? |
| | PLEASE CORRELATE AND CORRECT. |
| | |
| | 2)NOTE: PLEASE SEE THAT NOC SUBMITTED |
| | HAS SINCE EXPIRED. NOC IOS FROM JAN 2001 |
| | A NEW RECORDED NOC WILL BE REQ'D BEFORE |
| | PICKING UP PERMIT. |
| | |
| | 3)NOTE: PLEASE SEE THAT SD'S ARE STILL |
| | MISSING INSIDE BEDROOMS, INCLUDING DEN, |
| | WHICH IS AN ADAPTABLE BEDRM. |
| | NFPA-72 |
| | |
| | 4)NOTE: PLEASE SEE THAT PLANS NEED TO BE |
| | STAMPED FROM HISTORIC AGAIN. NEW SETS |
| | WERE SUBMITTED AND CHANGES MADE. ALSO |
| | NEEDS TO GO BACK TO OTHER TRADES DUE TO |
| | NEW PLANS AND CHANGES MADE. |
| | |
| | 5)NOTE: PLEASE SEE MISSING RECEPT ON |
| | KITCHEN COUNTERSPACE PER 210.52C1 |
| | NEXT TO STOVE. |
| | |
| | 6)NOTE: PLEASE SEE THAT LOAD CALCULATION |
| | -S WERE NOT SUBMITTED AND MISSING FROM |
| | SETS? 215.5 |
| | PLEASE SHOW SERVICE LOCATION."ON MAIN |
| | HOUSE? |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | PLEASE SEE THAT ONLY A 90 DAY EXTENTION |
| | HAS BEEN GRANTED BY THE BLDG OFFICAL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |