Plan Review Notes
Plan Review Notes For Permit 02120463
Permit Number 02120463
Review Stop E
Sequence Number 2
Notes
Date Text
2003-09-15 00:00:00************* UNSAT ******************
  
 1)NOTE: PLEASE SEE THAT ORIG PERMIT
 APPLICATION DID NOT COME BACK IN W/
 PACKAGE. PLEASE SUBMIT PERMIT APPL.
 PLEASE ALSO SEE THAT PLANS ARE STILL
 SHOWING 710 PARK PL??? PERMIT APPL AND
 PROPERTY ID USED IS FOR 712 PK PL??
 PLEASE SEE THAT WORK WAS ALREADY DONE ON
 712 ON PREVIOUS PERMITS?
 PLEASE CORRELATE AND CORRECT.
  
 2)NOTE: PLEASE SEE THAT NOC SUBMITTED
 HAS SINCE EXPIRED. NOC IOS FROM JAN 2001
 A NEW RECORDED NOC WILL BE REQ'D BEFORE
 PICKING UP PERMIT.
  
 3)NOTE: PLEASE SEE THAT SD'S ARE STILL
 MISSING INSIDE BEDROOMS, INCLUDING DEN,
 WHICH IS AN ADAPTABLE BEDRM.
 NFPA-72
  
 4)NOTE: PLEASE SEE THAT PLANS NEED TO BE
 STAMPED FROM HISTORIC AGAIN. NEW SETS
 WERE SUBMITTED AND CHANGES MADE. ALSO
 NEEDS TO GO BACK TO OTHER TRADES DUE TO
 NEW PLANS AND CHANGES MADE.
  
 5)NOTE: PLEASE SEE MISSING RECEPT ON
 KITCHEN COUNTERSPACE PER 210.52C1
 NEXT TO STOVE.
  
 6)NOTE: PLEASE SEE THAT LOAD CALCULATION
 -S WERE NOT SUBMITTED AND MISSING FROM
 SETS? 215.5
 PLEASE SHOW SERVICE LOCATION."ON MAIN
 HOUSE?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
 PLEASE SEE THAT ONLY A 90 DAY EXTENTION
 HAS BEEN GRANTED BY THE BLDG OFFICAL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]