| 2003-01-03 00:00:00 | ************* UNSAT *************** |
| | |
| | PLEASE NOTE, ADDRESS ON PLANS SHOW 710 |
| | PARL PL.? PLEASE NOTE SURVEY AND LEGAL |
| | ADDRESS FOR BLDG IN PALM BEACH PROPERTY |
| | APPR. OFFICE IS LISTED AS 712? PLEASE |
| | CLARIFY HOW THIS KEEPS BEING APPLIED FOR |
| | UNDER 710? |
| | PLEASE ALSO NOTE CODES HAVE CHANGED |
| | SINCE THIS FIRST CAME IN, WHICH WILL |
| | HAVE AN AFFECT ON OTHER TRADES AND |
| | REVIEW COMMENTS ORIGINALLY SET FORTH |
| | UNDER OLD PERMIT # WHICH EXPIRED. |
| | |
| | 1)NOTE: PLEASE NOTE MISSING SD AT THE |
| | LOWER LEVEL IN THE VICINITY OF STAIRS. |
| | NFPA-72 8-1.4 |
| | PLEASE ALSO NOTE MISSING TWO SD'S ON |
| | SECOND FLR, OUTSIDE BEDROOMS AND SD |
| | THAT NEEDS TO MOVED TO UPPER LEVEL OF |
| | STAIRS OUTSIDE SLEEPING ROOMS.NFPA-72 |
| | |
| | 2)NOTE: PLEASE CLARIFY WHAT APPEARS TO |
| | BE AN "ISLAND IN KITCHEN? IF SO, PLEASE |
| | SEE 210-52-C-2 ALSO TO BE GFI. |
| | |
| | 3)NOTE: PLEASE CLARIFY PLANS SHOWING |
| | ALL GFI RECEPTS IN BEDROOMS? SINCE PLANS |
| | FIRST CAME THROUGH FOR REVIEW. AS OF |
| | JAN 1ST 2002, ARC FAULT BRKRS ARE REQ`D |
| | FOR ALL BEDROOM CIRCUITS AND ARE LISTED |
| | ON PANEL SCHEDULE. PER 210-12 NEC. |
| | |
| | 4)NOTE: PLEASE CLARIFY HOW 2-5KW HEAT |
| | STRIPS ARE SHOWN AS 5600W ON LOAD CALCS? |
| | |
| | 5)NOTE: PLEASE CLARIFY EQUIPMENT OUTSIDE |
| | GUEST RM. SHOWS A 220V AND 120V RECEPT? |
| | PLEASE NOTE, 2 AHU`S ARE ALREADY SHOWN. |
| | |
| | JUST A NOTE, IF THERE ARE GOING TO BE |
| | ANY CATV, TELEPHONE ORLOW SYSTEMS |
| | INSTALLED, PLEASE SHOW ON PLANS IN |
| | ORDER TO BE INCLUDED ON THIS APPLICATION |
| | PLEASE NOTE, IF DONE AT LATER DATE, |
| | SEPARATE PERMIT APPLICATION/PLANS WILL |
| | BE REQ`D. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |