Plan Review Notes
Plan Review Notes For Permit 02120461
Permit Number 02120461
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-12-18 00:00:001) THE EMERGENCY VOICE MESSAGE IS TO
 BE REVISED, CHANGE THE WORD FIRE TO AN
 EMERGENCY HAS BEEN REPORTED. ALSO ADD
 DO NOT USE THE ELEVATORS.
  
 2) PLEASE PROVIDE A COPY OF THE SIGNED
 CONTRACT FOR THE FIRE ALARM SYSTEM.
 THE VALUE OF THE JOB SHOULD INCLUDE
 ALL PARTS AND LABOR.
  
 3) PLEASE ADD A NOTE TO THE PLANS, THAT
 FIRE ALARM DEVICES ARE NOT TO BE
 INSTALLED UNTIL FINAL TRADE CLEAN-UP
 HAS BEEN PERFORMED.
  
 4) PLEASE ADD A NOTE TO THE PLANS, THAT
 THE FIRE ALARM SYSTEM IS TO BE
 COMPLETELY TESTED AND APPROVED PRIOR TO
 SCHEDULING AN INSPECTION WITH FIRE
 RESCUE PERSONNEL.
  
 5) PLANS DO NOT REFLECT TAMPER SWITCHES
 FOR ANY EXTERIOR BACKFLOW DEVICE CONTROL
 VALVES FOR THE FIRE SYSTEM. PLEASE
 INDICATE THIS ON THE PLANS.
  
 6) WHERE ARE THE TAMPER SWITCHES FOR
 THE TRASH CHUTE AND ELEVATOR SPRINKLER
 PIPING.
  
 7) ALL ROOMS PLANNED FOR THE HANDICAPPED
 MUST BE EQUIPPED WITH SPEAKER STROBES.
 PLEASE ADVISE LOCATIONS.
  
 8) THE REQUIRED FIRE ALARM SYSTEM IS
 TO BE MONITORED BY A LICENSED UL LISTED
 CENTRAL STATION APPROVED BY THE FIRE
 RESCUE DEPARTMENT. SIGNALS THAT ARE TO
 BE RECEIVED INCLUDE GENERAL ALARM,
 SUPERVISORY, TROUBLE, AND WATERFLOW
 ALARM.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910