Plan Review Notes
Plan Review Notes For Permit 02120313
Permit Number 02120313
Review Stop R
Sequence Number 1
Notes
Date Text
2003-01-08 00:00:00BUILDING DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE ENERGY CALCULATION FORM IS
 REQUIRED TO BE SIGNED BY THE OWNER/AGENT
  
 3) THE UPLIFTS GIVEN ON THE ROOF FRAMING
 PLAN ON S2, EXCEED THE CAPACITIES OF THE
 SPECIFIED CONNECTORS AT SEVERAL
 LOCATIONS. SEE REDLINES ON PLANS.
  
 4) CLARIFY THE CONNECTOR AND THE UPLIFT
 FOR THE HIP GIRDER OVER THE GARAGE. THE
 OUTER END HAS 1588# OF UPLIFT AND B ON
 S2 CONNECTOR IS SPECIFIED. THE CONNECTOR
 OON THE OTHER END (ENTRY) IS A USP MSH
 WHICH HAS A UPLIFT CAPACITY OF 785#.
 PLEASE REVIEW.
  
 5) THE ROOF NAILING ZONE FOR THE GABLE
 END OVER BEDROOM #2 IS ZONE 3 FOR 4'
 FROM GABLE PLUS OVERHANG. PLEASE CORRECT
 THE DIAGRAM ON S2.
  
 6) ACCORDING TO THE STORM PANEL KEY PLAN
 UNITS 1 & 2 ON THE INSTALLATION SCHEDULE
 ARE REVERSED. UNIT 6 (2) SH 25 WITH 24"
 TRANSOM ABOVE HAS THE WRONG OPENING SIZE
 LISTED ON THE SCHEDULE. THE OPENING SIZE
 FOR UNIT 8 IS ALSO INCORRECT.
  
 7)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - SLIDING GLASS DOORS
 - SINGLE OUTSWING DOOR WITH ONE SIDELITE
 - ARCHED TOP WINDOW (BEDROOM #2)
  
 8) PROVIDE A SOIL BEARING TEST REPORT AS
 REQUIRED BY FBC 1804.2.2.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202
  
 659-8096 EXT.8202