| 2003-01-10 00:00:00 | BUILDING DENIED |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) FL BLD CODE 1804.2.2 QUESTIONABLE |
| | SOILS, WHERE THE BEARING CAPACITY IS |
| | NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| | PROVIDE SOIL REPORT. |
| | |
| | 3) DRYER VENT CAN NOT PENETRATE THROUGH |
| | THE ONE HOUR FIRE RATED WALL ON THE |
| | ZERO LOT LINE. TABLE 600 OF THE FBC DOES |
| | NOT ALLOW ANY OPENINGS IN A WALL WITHIN |
| | THREE FEET OF THE PROPERTY LINE. |
| | |
| | 4) SECTION 2 ONS1 IS MISLABELED AS 2 |
| | ON S2. PLEASE CORRECT. |
| | |
| | 5) THE USP TA24 CONNECTORS SPECIFIED ON |
| | S2 FOR THE TRUSSES AT THE COVERED PORCH |
| | AND ON THE BUILDING SECTION ON A4 FOR |
| | THE ATTACHMENT OF FLOOR TRUSSES TO THE |
| | LEDGER ARE NOT THE PROPER ANCHORS. THESE |
| | ARE EMBED TYPE ANCHORS AND NOT WOOD TO |
| | WOOD STRAPS. PLEASE CORRECT. |
| | |
| | 6) PROVIDE ADDITIONAL DETAILS FOR THE |
| | WOOD DECK ABOVE THE ENTRY. INDICATE THE |
| | CONNECTORS FOR THE 2X10 JOISTS, THE |
| | SHEATHING, ROOF COVERING MATERIAL, ETC. |
| | |
| | 7) THE ENERGY CALCULATIONS ARE REQUIRED |
| | TO BE SIGNED BY THE OWNER/AGENT. THE |
| | CONDITION SPACE ON THE ENERGY CALC. FORM |
| | DOES NOT AGREE WITH THE A/C AREA LISTED |
| | ON THE PLANS. PLEASE CORRECT. |
| | |
| | 8) THE STORM PANEL INSTALLATION |
| | SCHEDULE AND KEY PLAN SUBMITTED DOES NOT |
| | CORRESPOND TO THIS MODEL. |
| | |
| | 9) PROVIDE A STRUCTURAL DETAIL FOR THE |
| | BOLLARD USED TO PROTECT THE WATER HEATER |
| | IN THE GARAGE. |
| | |
| | 10) PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - SLIDING GLASS DOORS |
| | - SINGLE HUNG WINDOWS |
| | - ARCHED FIXED GLASS WINDOWS |
| | NOTE: PRODUCT APPROVAL FOR ROOF TILE |
| | EXPIRED ON 12/16/02. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |