2002-12-24 00:00:00********* NOTES REDLINED *********
  
 1)SD TO BE A MIN OF 3' FROM KITCHEN
 AREA. NFPA-72 8-1.4.1.6
  
 2)CONDUCTORS FROM 200A MAIN SHOWN AS
 #6 AND CONDUCTORS FEEDING 60A SUB PANEL
 SHOWN AS 2/0'S. SEEM TO BE REVERSED.
  
 IF THERE ARE ANY QUESTIONS,PLEASE CALL.
  