| Plan Review Notes For Permit 02120281 |
| Permit Number |
02120281 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-12-24 00:00:00 | ********* NOTES REDLINED ********* | | | | | | 1)SD TO BE A MIN OF 3' FROM KITCHEN | | | AREA. NFPA-72 8-1.4.1.6 | | | | | | 2)CONDUCTORS FROM 200A MAIN SHOWN AS | | | #6 AND CONDUCTORS FEEDING 60A SUB PANEL | | | SHOWN AS 2/0'S. SEEM TO BE REVERSED. | | | | | | IF THERE ARE ANY QUESTIONS,PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|