| Plan Review Notes For Permit 02120180 |
| Permit Number |
02120180 |
|
| Review Stop |
R |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-01-13 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1-PROVIDE COMPLETE INFORMATION FOR STORM | | | SHUTTERS UNDER A SEPARATE PERMIT. | | | 2-PROVIDE SOIL TEST REPORT. | | | 3-FLOOD ZONE A8: WILL NEED THE ELEVATION | | | CERTIFICATE. | | | 4-CLARIFY DETAIL S21 FOR COLUMN LOCATED | | | BETWEEN GARAGE AND STAIRWAY SHOWING | | | HOW IS THE STRAP HOLDING THE 2 GIRDER | | | TRUSSES. SEC. 104.2.1.2 CITY AMENDMENT | | | 5-REVISE CONNECTOR TC-1 SPECIFIED ON | | | ROOF FRAMING PLAN AT FRONT ELEVATION. | | | NEED WOOD TO WOOD CONNECTOR FOR FRAMED | | | WALL. SEC. 104.2.1.2 CITY AMENDMENTS. | | | 6-REVISE STAIR TOP DETAIL ON SHEET A-4 | | | TO MATCH 2ND FLOOR FRAMING PLAN AND | | | SPECIFY FIREBLOCKING AS REQUIRED BY | | | SEC. 2305.1.4 FBC 2001. | | | 7-34SH WINDOW DOESN'T PROVIDE THE 24" | | | MIN. CLEAR HEIGHT. ALSO, VERIFY THAT | | | 24+5 SH WINDOW PROVIDE THE 5.7 S.F. | | | MIN. CLEAR OPENING. SEC. 1005.4.4 FBC |
|