| Plan Review Notes For Permit 02120137 |
| Permit Number |
02120137 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-03-31 00:00:00 | DENIED: | | | | | | COMMENTS FROM 1ST REVIEW NOT ADDRESSED. | | | PROVIDE MANUAL J CALCS AS PER 2001 FBC | | | CHAPTER 13 SECTION 607.1.ABC.1, | | | EQUIPMENT SIZING.PROVIDE INFORMATION | | | OF HVAC EQUIPMENT (MAKE, MODEL, BTU OF | | | THE AHU & SEER OF THE CONDENSING UNIT). | | | | | | NO MECHANICAL PLANS INDICATING DUCT LAY- | | | OUT OF LOCATION OF AHU'S OR CONDENSING | | | UNITS SUBMITTED FOR REVIEW. | | | | | | SMOKE DETECTORS SHALL BE INSTALLED | | | SUPPLY SYSTEMS WITH A DESIGN CAPACITY | | | GREATER THAN 2,000 CFM, IN THE SUPPLY | | | AIR DUCT. 2001 FBC(M) 606.2.1OR | | | UPON ACTIVATION, THE SMOKE DETECTORS | | | SHALL SHUTDOWN THE AIR DISTRIBUTION | | | SYSTEM. 2001 FBC(M) 606.4 | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|