| Plan Review Notes For Permit 02120137 |
| Permit Number |
02120137 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-03-24 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | 1} THERE ARE NO SMOKE DETECTORS ON | | | SHEET E-4.PLEASE SHOW COMPLIANCE WITH | | | 8-1.4.1.6 NFPA-72. | | | | | | 2} PLEASE NOTE THAT THE PANELS SHOWN IN | | | THE CLOSET ON SHEET E-3(A,B,C,SB,AND | | | LV'S) MUST COMPLY WITH110-26. | | | | | | 3} THE SMOKE DETECTOR @ THE DOORWAY | | | OF THE MASTER BEDROOM JUST AT THE | | | HALL APPEARS TO BE INSIDE THE AREA OF | | | THE MASTER BEDROOM AND WOULD THEREFORE | | | NOT BE IN COMPLIANCE WITH 8-1.4.2 | | | NFPA-72,AS BEING LOCATED "OUTSIDE". | | | | | | THESE THREE COMMENTS WERE ON THE LAST | | | REVIEW,IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096.EXT 8392. |
|