| 2003-01-21 00:00:00 | UNSAT |
| | ~~~~~ |
| | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| | PLEASE PROVIDE THE FOLLOWING |
| | INFORMATION,MAKE ANY NECESSARY CHANGE |
| | ON PLANS AND RESUBMIT FOR REVIEW. |
| | |
| | 1} PLEASE NOTE THAT ALL PLANS |
| | THAT ARE SIGNED AND SEALED BY ARCH/ OR |
| | ENGINEER ARE REQ`D PER 61G15-23.002 FOR |
| | ENGINEER AND 61G1-16.004 FOR ARCH. |
| | SHALL HAVE A TITLE BLOCK. |
| | |
| | 2} PLEASE INDICATE THE AMPERE RATING OF |
| | THE METER ENCLOSURE. |
| | |
| | 3} PLEASE INDICATE THE CONDUCTOR AND |
| | WIRE SIZE FROM THE METER TO THE M.D.P. |
| | |
| | 4} THE FEEDER CONDUCTORS TO PANEL "N" |
| | ARE SHOWN AS NUMBER 1 ON MDP SCHEDULE |
| | AND 2/0'S ON THE RISER DIAGRAM.PLEASE |
| | CLARIFY. |
| | |
| | 5} THE FEEDER CONDUCTORS TO PANEL "C" |
| | ARE SHOWN AS 3/0'S ON THE PANEL |
| | SCHEDULE AND 2/0 ON THE RISER |
| | DIAGRAM,PLEASE CLARIFY. |
| | |
| | 6} THERE ARE NO SMOKE DETECTORS ON |
| | SHEET E4.PLEASE SHOW COMPLIANCE WITH |
| | 8-1.4.1.6 NFPA-72. |
| | |
| | 7} PLEASE NOTE THAT THE PANELS SHOWN IN |
| | THE CLOSET ON SHEET E3(A,B,C,SB AND LV'S |
| | MUST COMPLY WITH 110-26. |
| | |
| | 8} THE SMOKE DETECTOR @ THE DOORWAY OF |
| | THE MASTER BEDROOM JUST AT THE |
| | HALL,APPEARS TO BE INSIDE THE AREA OF |
| | THE MASTER BEDROOM AND WOULD THEREFORE |
| | NOT BE IN COMPLIANCE 8-1.4.2 NFPA-72,AS |
| | BEING LOCATED "OUTSIDE". |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/659-8096 EXT. 8392. |