| Plan Review Notes For Permit 02120132 |
| Permit Number |
02120132 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2003-03-25 00:00:00 | BUILDING PLAN REVIEW | | | ******PROVISO******* | | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | | | --PROVISO-- | | | THE SUBMITTED STORE FRONT DOOR PRODUCT | | | APPROVAL NOA# 01-0919.02 IS FOR SINGLE | | | UNIT APPLICATIONS ONLY, AND SO DOES NOT | | | COVER THE MULLED SIDELITES ADJACENT | | | DOOR #1.STRUCTURAL MULLIONS ARE | | | REQUIRED. ALSO, THE SIDELITES EXCEED THE | | | 96" MAX. HEIGHT COVERED BY THE WINDOW | | | WALL SYSTEM PRODUCT APPROVAL | | | NOA# 01-0329.02, SO A HORIZONTAL MULLION | | | IS REQUIRED.SUBMIT AN APPROPRIATE | | | STRUCTURAL MULLION PRODUCT APPROVAL OR | | | SITE SPECIFIC ENGINEERING. |
|