| Plan Review Notes For Permit 02120132 |
| Permit Number |
02120132 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-03-20 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | | | | 1) FROM PREVIOUS REVIEW, SHT PO.1 THERM- | | | AL EXPANSION CONTROL REQUIRED PER SEC. | | | 607.3.2. PLEASE SHOW ON W/H'S #1 & #2. | | | SHEETS WERE NOT CHANGED. | | | 2) FROM PREVIOUS REVIEW, SHT P6.1 WATER | | | RISER DIAGRAM, WATER HAMMER ARRESTORS | | | REQUIRED BY SEC 604.9 SHALL BE LOCATED | | | NEAR THE FIXTURES IN AN "EFFECTIVE RANGE | | | NOT AT THE TOP OF DROPS IN THE CEILING | | | AS SHOWN. PDI-WH 201 AND MANUF. INSTALL- | | | ATION INSTRUCTIONS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|