| Plan Review Notes For Permit 02120132 |
| Permit Number |
02120132 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-12-30 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | | | | 1) STH A.7 PRIVATE TOILET ROOM FOR EXEC. | | | SHALL BE ADAPTABLE PER 11-4.1.3(11). | | | SHOW DETAIL FOR GRAB BAR BACKING, OPEN- | | | ING FOR W/C, LAV HEIGHT (34") ECT. | | | 2) SHT A.9 BREAK ROOM ELEVATIONS #'S 1 & | | | 2. SINKS SHALL COMPLY WITH 11-4.24 AND | | | ALL SUBSECTIONS. PLEASE SHOW DETAILS. | | | 3) SHT P0.1 THERMAL EXPANSION CONTROL | | | REQUIRED PER SEC 607.3.2. PLEASE SHOW | | | ON WATER HEATER DETAIL EWH #1 & EWH #2. | | | 4) SHT P2.1 - RELIEF VENT REQUIRED ON | | | CONDENSATE LINE AS IT EXITS BLDG. | | | 5) SHT P6.1 WATER RISER DIAGRAM, WATER | | | HAMMER ARRESTORS REQUIRED BY 604.9 SHALL | | | BE LOCATED NEAR THE FIXTURES IN AN | | | "EFFICTIVE RANGE" NOT AT TOP OF DROPS IN | | | CEILING AS SHOWN. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|