Plan Review Notes
Plan Review Notes For Permit 02120090
Permit Number 02120090
Review Stop E
Sequence Number 1
Notes
Date Text
2002-12-09 00:00:00************ UNSAT *******************
  
 1)NOTE: PLEASE NOTE CIRCUITING FOR
 EM/EX LTS NEED TO BE ON THE SAME CIRCUIT
 (S) AS LIGHTING ON THOSE AREAS.
 700-12E
  
 2)NOTW: PLEASE NOTE, NO PANEL SCHEDULES
 SUBMITTED FOR NEW PANELS?
 PLEASE SUBMIT AND CORRELATE WITH PLANS.
  
 3)NOTE: PLEASE SUBMIT LOAD CALCUALTIONS
 FOR ENTIRE SERVICE. PLEASE NOTE,
 RISER MENTIONS A EXIST 800A SERVICE
 COMING IN. PLEASE NOTE 300MCM ARE
 ONLY RATED AT 285A`S PER 310-16/110-14
 THIS PUTS SERVICE AT 600A`S.
 NO LOAD CALCS WERE SUBMITTED FOR NEW
 PANELS AND LOADS BEING ADDED.
 PLEASE NOTE, ALL CONTINUOS LOADS AT 125%
  
 4)NOTE: PLEASE SEE RISER DIAGRAM, SHOWS
 #2 BEING FED TO 200A DSIC AND CHNAGE
 AHS BEEN HAND WRITTEN ON PLAN CHANGING
 FROM 100A TO 200A.
 PLEASE NOTE, ANY HANDWRITTEN CHANGES ON'
 PLANS, MUST BE DONE BY THE ARCH OF
 RECORD. 481.221.
  
 5)NOTE: PLEASE CLARIFY MEANS OF EQUIP-
 -MENT GROUNDING BETWEEN MAIN DISC`S AND
 PANELS. SIZE PER 250-122
  
  
 PLEASE SUBMIT THE ABOVE INFORMAITON FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  