Plan Review Notes
Plan Review Notes For Permit 02120042
Permit Number 02120042
Review Stop E
Sequence Number 1
Notes
Date Text
2003-01-03 00:00:00************* UNSAT ******************
  
 1)NOTE: PLEASE SUBMIT AIC RATING(S) FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 110-9/215-5
  
 2)NOTE: PLEASE CLARFIFY EXACT LENGTH OF
 CONDUCTORS GOING OVERHEAD "INSIDE" THE
 BLDG. PLEASE NOTE PER 210-70 LOCAL
 AMENDMENTS, NO MORETHAN 8" OF UNPROTECT-
 ED CONDUCTORS INSIDE PERMITTED.
  
 3)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTED CIRCUITS PER 210-12 ON PANEL
 SCHEDULE.
  
  
 4)NOTE: PLEASE NOTE MISSING EQUIPMENT
 GROUNDING CONDUCTORS BETWEEN PANEL AND
 A/C UNITS.
  
 5)NOTE: PLEASE NOTE MISSING FRONT AND
 REAR RECEPTS PER 210-52E
  
  
 6)NOTE: PLEASE SHOW NEUTRAL LOAD CALCS
 FOR DOWN SIZING NEUTRAL.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW, IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372