| 2003-01-14 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | 1) FBC 3401.7.2.6AS THE COST OF THE |
| | PROPOSED REPAIRS AND ALTERATIONS EXCEED |
| | 50% OF THE VALUE OF THE EXISTING |
| | BUILDING,THE BUILDING SHALL BE MADE TO |
| | CONFORM TO THE CODE REQUIREMENTS FOR A |
| | NEW BUILDING, WITH THE STRUCTURAL |
| | EXCEPTIONS LISTED IN THIS SECTION OF THE |
| | CODE.MORE INFORMATION IS REQUIRED ON |
| | THE PLANS, TO DEMONSTRATE COMPLIANCE. |
| | |
| | 2) FBC* 101.4.2 AMEND THE PLANS TO STATE |
| | THAT THE PROPOSED WORK IS DESIGNED TO |
| | FLORIDA BUILDING CODE 2001. |
| | |
| | 3) FBC 13-103.0ENERGY CODE COMPLIANCE |
| | SHALL BE DEMONSTRATED BY SUBMITTAL OF |
| | APPROPRIATE CODE COMPLIANCE FORMS (REF: |
| | COMMENT 1) |
| | |
| | 4) FBC 1606.1.7WIND LOAD.THE PLANS |
| | SHALL STATE THE BASIC WIND SPEED, WIND |
| | IMPORTANCE FACTOR, WIND EXPOSURE |
| | CATEGORY, INTERNAL PRESSURE COEFFICIENT, |
| | AND EXTERIOR COMPONENT AND CLADDING |
| | DESIGN WIND PRESSURES. |
| | |
| | 5) WINDOW PRODUCT APPROVAL.THE WINDOW |
| | SCHEDULE,ON DRAWING SHEET 1, SPECIFIES |
| | 'PGT' SINGLE HUNG WINDOWS AS INDICATED |
| | ON THE ELEVATIONS.THE SUBMITTED 'PGT' |
| | PRODUCT APPROVAL NOA# 02-0327.04 IS FOR |
| | CASEMENT WINDOWS AND THEREFOR IS NOT |
| | APPLICABLE.SUBMIT AN APPROPRIATE |
| | WINDOW PRODUCT APPROVAL. |
| | |
| | 6) FBC 1707.4.5.1THE PROPOSED WINDOW |
| | MULLIONS SHALL BE PART OF THE WINDOW |
| | PRODUCT APPROVAL TO BE SUBMITTED, OR |
| | SHALL BE SUBJECT OF A SEPARATE PRODUCT |
| | APPROVAL. |
| | |
| | 7) FBC 1707.4SUBMIT A PRODUCT |
| | APPROVAL FOR THE NEW EXTERIOR DOOR. |
| | |
| | 8) FBC* 104.2.1.2FROM DETAILS 1, 2 & 3 |
| | ON SHEET 2, IT APPEARS THAT THE EXISTING |
| | ROOF SPANS IN THE EAST-WEST DIRECTION. |
| | THE PROPOSED ROOF SUPPORT SCHEME WILL |
| | REDIRECT THE ROOF LOADS TO THE NORTH AND |
| | SOUTH WALLS WHICH WERE NOT PREVIOUSLY |
| | LOADED THAT WAY. SUBMIT FURTHER DETAILS, |
| | INCLUDING THE HEADER ARRANGEMENT OVER |
| | THE WINDOWS AND DOORS IN THE NORTH AND |
| | SOUTH WALLS, TO JUSTIFY THE PROPOSAL. |
| | |
| | 9) FBC 1707.4.4.3WINDOW AND DOOR BUCKS |
| | SUBMIT DETAILS TO SHOW ANCHORING OF THE |
| | DOORS AND WINDOWS TO THEIR ROUGH OPENING |
| | |
| | 10) IF NEW PLAN SHEETS ARE REQUIRED, IN |
| | ORDER TO ADDRESS THE ABOVE COMMENTS, THE |
| | OLD SHEETS SHALL BE REMOVED AND THE NEW |
| | SHEETS INSERTED.ONE COPY OF EACH OLD |
| | SHEET SHALL BE INCLUDED WITH THE |
| | RESUBMITTAL FOR COMPARISON OF REVISIONS. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |