| Plan Review Notes For Permit 02120009 |
| Permit Number |
02120009 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-01-03 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE NOTE THE FOLLOWING DISCREPANCIES | | | MAKE ANY NECESSARY CORRECTIONS ON THE | | | PLANS AND RESUBMIT FOR REVIEW. | | | | | | 1} THE DISCONNECT ON THE RISER DIAGRAM | | | IS 300 AMPS,BEING FED WITH #2/0(200AMP) | | | CONDUCTORS. THE LOAD CALCULATION IS IN | | | EXCESS OF 200 AMPS. PLEASE CORRELATE | | | OCP,CONDUCTORS,LOAD CALCULATION AND | | | EQUIPMENT GROUND TO REFLECT WHAT IS TO | | | BE INSTALLED. | | | | | | 2} THE CABANA BATH NEEDS A RECEPTACLE TO | | | COMPLY WITH 210-11(C)(3),MUST BE GFI. | | | | | | 3} MASTER & BATH #2 NEEDS A RECEPTACLE | | | ADDED TO COMPLY WITH 210-52(D). | | | | | | 4} BEDROOM #5 NEEDS TO HAVE SMOKE | | | DETECTORS TO COMPLY 8-1.4.1.6.2(1) & | | | (2). | | | | | | 5} AHU & WATER HEATER DISCONNECTS IN THE | | | GARAGE MUST COMPLY WITH 110-26. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT. 8392 |
|