1 |
|
| Notes |
| Date |
Text |
| 2002-12-26 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | | | | 1) PER TABLE 403.1 MINIMUM OF 2 DRINKING | | | FOUNTAINS ARE REQUIRED. 1 FOR WAREHOUSE | | | AND 1 FOR BUSINESS/SHOWROOM AREA. ALSO | | | SEE SECTION 410.1 | | | 2) PLEASE PROVIDE A SANITARY RISER DIA- | | | GRAM AND A WATER RISER DIAGRAM. | | | 3) WILL THERE BE ANY FOOD COOKED OR | | | SERVED AT THE DEMO KITCHEN? | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|