| Plan Review Notes For Permit 02111907 |
| Permit Number |
02111907 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-12-27 00:00:00 | DENIED: | | | | | | PLAN SHEET 3.2 INDICATES OUTSIDE AIR | | | CALCULATION (#4) 2437 SQ FT @ .3 CFM PER | | | FT.IS THIS CALCULATION FOR THE SPACE | | | MARKED 130 OR 129 ON SHEET 1.0?PLEASE | | | PROVIDE OUTSIDE AIR CALCULATIONS FOR ALL | | | AREAS. | | | | | | EXHAUST FAN #2 IS NOT LISTED ON THE | | | FAN SCHEDULE.PLEASE IDENTIFY. | | | | | | PROVIDE INFORMATION ON THE CONDENSATE. | | | INDICATE TERMINATION LOCATIONS.UNITS | | | LARGER THAN 6 TONS SHALL DICHARGE TO | | | STORM DRAIN OR DRY WELL. | | | | | | FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | | SHALL HAVE: | | | ACTIVATION OF ANY AIR DISTRIBUTION | | | SYSTEM SMOKE DETECTOR CAUSES A | | | SUPERVISORY SIGNAL TO BE INDICATED AT | | | A CONSTANTLY ATTENDED LOCATION OR SHALL | | | HAVE AN ALARM/STROBE IN NORMALLY | | | OCCUPIED AREA.NFPA 90A 4-4.4.2 OR | | | 4-4.4.3 (A). | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|