| Plan Review Notes For Permit 02111907 |
| Permit Number |
02111907 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-12-05 00:00:00 | ************* UNSAT **************** | | | | | | 1)NOTE: PLEASE CLARIFY DIRECTION OF | | | PANELS. PANELS SEEM TO BE FACING RM | | | 112 AND NOT IN THE SAME LOCATION OF | | | TRANSFORMER? | | | | | | 2)NOTE: PLEASE NOTE MISSING EQUIPMENT | | | GROUNDING CONDUCTOR BETWEEN PANEL "H1" | | | TRANSFORMER AND PANELS "L1 AND "L". | | | 250-122/250-24/250-30 | | | PLEASE ALSO SHOW EQUIPMENT GROUNDING | | | MEANS BETWEEN | | | | | | 3)NOTE: PLEASE CLARIFY/ NEW OR EXSITNG | | | SHOW WINDOW RECEPTS PER 210-62 | | | | | | 4)NOTE: PLEASE CLARIFY CIRCUITING FOR | | | EM LT/ EXT LTS SHOWN PER 700-12E. | | | | | | PLEASE SUBMIT THE ABOVE INFOMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|