| Plan Review Notes For Permit 02111818 |
| Permit Number |
02111818 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-12-26 00:00:00 | **************UNSAT ************* | | | | | | 1)NOTE: PLEASE SEE LOAD CALCULATIONS | | | SUBMITTED, LOAD IS SHOWN AT 223A W/ A | | | 200A METERCAN ENCLOSURE?? | | | PLEASE ALSO NOTE, LOAD CALCS STILL DO | | | NOT INCLUDE HEAT PUMP IN LOAD AND | | | SIZING OF UNIT. | | | SPECS ARE SUBMITTED FOR HEAT PUMP SHOW- | | | -ING 6 DIFFERENT SIZES???? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|