| Plan Review Notes For Permit 02111723 |
| Permit Number |
02111723 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-12-23 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | | | | 1) RPZ BACKFLOW REQUIRED. MAXIMUM 4' | | | ABOVE FINISHED FLOOR FOR SERVICE AND | | | TESTING. FLOOR SINK REQUIRED FOR INDIR- | | | ECT DRAINAGE FROM BACKFLOW. | | | 2) PLEASE SUBMIT A WATER RISER DIAGRAM. | | | IF SHOCK CONTROL USED IT WILL BE PER | | | SEC 604.9, AND WILL BE LOCATED NEAR THE | | | FIXTURE NOT AT THE TOP OF DROPS IN CEIL- | | | ING. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|