| Plan Review Notes For Permit 02111723 |
| Permit Number |
02111723 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-12-05 00:00:00 | ************** UNSAT ************* | | | | | | 1)NOTE: PLEASE CLARIFY LOADS. PLEASE | | | CLARFIY LOADS SHOWN AT 125% ARE 8@180? | | | WHICH LOAD ARE THESE? RECEPTS. PLEASE | | | NOTE LIGHTING ARE CONSIDERED CONTINUOUS | | | LOADS ALSO.IF 8@180 ARE RECEPTS?, PLEASE | | | VERIFY COUNT. | | | | | | 2)NOTE: PLEASE CLARIFY LOADS (KW) SHOWN | | | IN VOLTAGE COLUMN? | | | | | | 3)NOTE: PLEASE PROVIDE CIRCUITING ON | | | PLANS AND CORRELATE WITH PANEL SCHEDULE. | | | | | | 4)NOTE: PLEASE CLARIFY NEW OR EXSITNG | | | EM LTS. PLEASE ALSO VERIFY LTS REQ`D | | | ON SAME BRANCH CIRCUIT AS NORMAL LTS | | | PER 700-12E | | | | | | 5)NOTE: PLEASE CLARIFY NEW OR EXSITING | | | SIGN CIRCUIT PER 600-5. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|