Plan Review Notes
Plan Review Notes For Permit 02111723
Permit Number 02111723
Review Stop E
Sequence Number 1
Notes
Date Text
2002-12-05 00:00:00************** UNSAT *************
  
 1)NOTE: PLEASE CLARIFY LOADS. PLEASE
 CLARFIY LOADS SHOWN AT 125% ARE 8@180?
 WHICH LOAD ARE THESE? RECEPTS. PLEASE
 NOTE LIGHTING ARE CONSIDERED CONTINUOUS
 LOADS ALSO.IF 8@180 ARE RECEPTS?, PLEASE
 VERIFY COUNT.
  
 2)NOTE: PLEASE CLARIFY LOADS (KW) SHOWN
 IN VOLTAGE COLUMN?
  
 3)NOTE: PLEASE PROVIDE CIRCUITING ON
 PLANS AND CORRELATE WITH PANEL SCHEDULE.
  
 4)NOTE: PLEASE CLARIFY NEW OR EXSITNG
 EM LTS. PLEASE ALSO VERIFY LTS REQ`D
 ON SAME BRANCH CIRCUIT AS NORMAL LTS
 PER 700-12E
  
 5)NOTE: PLEASE CLARIFY NEW OR EXSITING
 SIGN CIRCUIT PER 600-5.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  