| 2003-04-10 00:00:00 | DENIED |
| | |
| | 1) SEPARATE PERMIT IS REQUIRED FOR THE |
| | SITE WALL. |
| | |
| | 2) SMOKE DETECTORS ARE REQUIRED TO BE |
| | LOCATED PER FBC 905.2.2. |
| | |
| | 3)SPECIFY ATTIC VENTILLATION AS REQUIRED |
| | BY FBC 2309.7. THE NET FREE VENT AREA |
| | FOR THE EXISTING SLOPED ROOF GIVEN IS |
| | NOT ADEQUATE. (PROVIDE CALCULATIONS) |
| | SPECIFY THE VENTS FOR THE FLAT ROOFS AT |
| | THE GARAGE AND HOUSE AND FOR THE SLOPED |
| | ROOF AT THE TOWER. |
| | |
| | 4) PROVIDE (2) COPIES OF A RECENT |
| | SURVEY. |
| | |
| | 5)PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - OUTSWING FIBERGLASS DOOR AT GARAGE |
| | - OUTSWING WOOD ENTRY DOOR AT FOYER |
| | - SINGLE HUNG WINDOWS |
| | PLANS SPECIFY ALL SINGLE HUNG WINDOWS. |
| | THE PRODUCT APPROVALS ARE REQUIRED TO BE |
| | APPROVED BY HISTORIC PRESEVATION. THE |
| | PRODUCT APPROVALS SUBMITTED WERE FOR |
| | FIXED WINDOWS AND CASEMENT WINDOWS. IF |
| | THESE ARE USED CHANGE PLANS AND HAVE |
| | APPROVED BY HISTORIC PRESERVATION. |
| | |
| | 6) A SEPARATE PERMIT WITH ADDITIONAL FEE |
| | WILL BE REQUIRED FOR ROOFING. IT WAS NOT |
| | SIGNED FOR ON THE APPLICATION. |
| | |
| | 7)SEVERAL OF THE TRUSSES ON SHEETS 7 & 8 |
| | HAVE CONNECTOR #3 SPECIFIED, HOWEVER |
| | THERE IS NO #3 LISTED IN THE CONNECTOR |
| | SCHEDULE. |
| | |
| | 8) ALL EXTERIOR GLAZING TO BE IMPACT |
| | RESISTANT OR PROTECTED WITH STORM PANELS |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |