2003-04-10 00:00:00DENIED
  
 1) SEPARATE PERMIT IS REQUIRED FOR THE
 SITE WALL.
  
 2) SMOKE DETECTORS ARE REQUIRED TO BE
 LOCATED PER FBC 905.2.2.
  
 3)SPECIFY ATTIC VENTILLATION AS REQUIRED
 BY FBC 2309.7. THE NET FREE VENT AREA
 FOR THE EXISTING SLOPED ROOF GIVEN IS
 NOT ADEQUATE. (PROVIDE CALCULATIONS)
 SPECIFY THE VENTS FOR THE FLAT ROOFS AT
 THE GARAGE AND HOUSE AND FOR THE SLOPED
 ROOF AT THE TOWER.
  
 4) PROVIDE (2) COPIES OF A RECENT
 SURVEY.
  
 5)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - OUTSWING FIBERGLASS DOOR AT GARAGE
 - OUTSWING WOOD ENTRY DOOR AT FOYER
 - SINGLE HUNG WINDOWS
 PLANS SPECIFY ALL SINGLE HUNG WINDOWS.
 THE PRODUCT APPROVALS ARE REQUIRED TO BE
 APPROVED BY HISTORIC PRESEVATION. THE
 PRODUCT APPROVALS SUBMITTED WERE FOR
 FIXED WINDOWS AND CASEMENT WINDOWS. IF
 THESE ARE USED CHANGE PLANS AND HAVE
 APPROVED BY HISTORIC PRESERVATION.
  
 6) A SEPARATE PERMIT WITH ADDITIONAL FEE
 WILL BE REQUIRED FOR ROOFING. IT WAS NOT
 SIGNED FOR ON THE APPLICATION.
  
 7)SEVERAL OF THE TRUSSES ON SHEETS 7 & 8
 HAVE CONNECTOR #3 SPECIFIED, HOWEVER
 THERE IS NO #3 LISTED IN THE CONNECTOR
 SCHEDULE.
  
 8) ALL EXTERIOR GLAZING TO BE IMPACT
 RESISTANT OR PROTECTED WITH STORM PANELS
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202